ROLLOUT
SWITCH
HEAT EXCHANGER
SECTION
Fig. 50 − 48PG03−14 Typical Gas Heating Section
(48PG03−07 Shown)
HEAT
EXCHANGER
SECTION
IGC BOARD
(HIDDEN)
MAIN BURNER
SECTION
Fig. 51 − 48PM16−28
Typical Gas Heating Section
Condenser and Evaporator−Fan Motor Bearings
The condenser-fan and evaporator-fan motors have permanently
sealed bearings, so no field lubrication is necessary.

Economizer or Manual Outside Air Damper

If blade adjustment is required, refer to unit or accessory
installation instructions.

Evaporator Fan Service and Replacement

The units feature a slide-out fan deck for easy servicing of the
indoor-fan motor, pulleys, belt, and bearings. To service
components in this section, perform the following procedure:
1. Turn off unit power.
2. Open the fan section access door.
3. Remove two no. 10 screws at front of slide-out fan deck.
Save screws. (See Fig. 52 or 53.)
INDUCED
DRAFT
MOTOR
COMBUSTION
FAN HOUSING
MAIN GAS
VALVE
MAIN BURNER SECTION
COMBUSTION
FAN HOUSING
INDUCED
DRAFT
MOTOR
MAIN GAS
VALVE
4. For 48/50PG03−14 units, disconnect the electrical wires
connected to the slide−out fan deck (supply air thermistor
and fan status switch if installed). Wires may be damaged if
not disconnected. For 48/50PM16−28 units, disconnect the
limit switch wires located on the right side of the fan deck
(48 series only). Other wires do not need to be
disconnected.
5. Fan deck can now be slid out to access serviceable
components.
CAUTION
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in damage to the
unit.
DO NOT SLIDE FAN DECK OUT PAST THE FAN
DECK STOP. If further access is required, the fan deck
must be supported. Make sure plugs and wiring are not
pinched between fan housing and unit sheet metal post.
6. To replace fan deck to operating position, slide fan deck
back into the unit. Secure with the two no. 10 screws
removed in Step 3.
7. Re-attach electrical wires.
8. Close fan section access door.
9. Restore power to unit.
MOTOR
MOUNTING
BASE
SCREW
(HIDDEN)
SLIDE-OUT
FAN DECK
Fig. 52 − 48/50PG03−14
Evaporator−Fan Motor Adjustment
FAN
PULLEY
LIMIT
SWITCH
QUICK
CONNECT
(48PM ONLY)
Fig. 53 − 48/50PM16−28
Evaporator−Fan Motor Adjustment
85
FAN DECK STOP
FAN
PULLEY
MOTOR
PULLEY
SCREW
MOTOR
PULLEY
(HIDDEN)
MOTOR
MOUNTING
BASE
SLIDE-OUT
FAN DECK