Carrier 48/50PG C03-14 Operation And Service Manual page 150

Single package rooftop units with comfortlink controls version 5.x and puron (r-410a) refrigerant
Table of Contents

Advertisement

1. Static pressure losses from accessories and options
(Humidi-MiZer system, economizer, etc.) must be added
to external static pressure before entering Fan Performance
table. Refer to Accessory/FIOP Static Pressure information.
2. Interpolation is permissible. Do not extrapolate.
3. Fan performance tables are based on wet coils, clean filters,
and casing losses. Gas heat losses are included for 48 series
units.
Fan Performance — 50PG14 Horizontal Units
GENERAL NOTES FOR FAN PERFORMANCE DATA TABLES
4. Extensive motor and drive testing on these units ensures
that the full horsepower range of the motor can be utilized
with confidence. Using the fan motors up to the bhp rating
shown will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected.
5. Use of a field-supplied motor may affect wire size.
Recalculate the unit power supply MCA and MOCP if
required. Contact your Carrier representative for details.
6. Use the following formula to calculate input watts:
Input Watts = Bhp x (746/Motor Eff)
150