Testing The Gfci Breaker - Cal Spas Avalon A526 Owner's Manual

Cal flame spa owner's manual
Table of Contents

Advertisement

Testing the GFCI Breaker

Test the GFCI breaker prior to first use and periodically when the spa is
powered. To test the GFCI breaker follow these instructions (spa should
be operating):
1.
Press the TEST button on the GFCI. The GFCI will trip and the spa will
shut off.
2.
Reset the GFCI breaker by switching the breaker to the full OFF posi-
tion, wait a moment, then turn the breaker back on. The spa should
have power again.
Configuring the 6300 Control System
The 6300 control system requires higher power than other 240V systems.
Dip switch #10 is factory set in the ON position. This causes the heater to
shut off when any pump is running in high speed. To allow the heater to
continue operating, dip switch #10 must be set to the OFF position.
To ensure your spa functions properly, ensure the following steps are per-
formed before starting your spa:
When installing the electrical system, use a 60 amp GFCI. Follow the
GFCI wiring diagram on the next page.
Have your dealer or installer set dip switch #10 to the OFF position on
the circuit board as shown below.
10
LTR20091024, Rev. A

Advertisement

Table of Contents
loading

Table of Contents