Carrier 39L Series Installation, Operation, And Start-Up Instructions page 41

Central station air-handling units with product integrated controls (pic)
Table of Contents

Advertisement

Table 3 — Thermistor Resistance vs. Temperature Values for Space Temperature Sensor, Return-Air
RESISTANCE
TEMP
RESISTANCE
(Ohms)
(F)
173,631.0
−30
168,222.0
−29
162,998.0
−28
157,954.0
−27
153,083.0
−26
148,378.0
−25
143,833.0
−24
139,442.0
−23
135,200.0
−22
131,101.0
−21
127,139.0
−20
123,310.0
−19
119,609.0
−18
116,031.0
−17
112,571.0
−16
109,226.0
−15
105,992.0
−14
108,863.0
−13
99,837.3
−12
96,910.2
−11
94,078.4
−10
91,338.6
−9
88,687.3
−8
86,121.6
−7
83,638.4
−6
81,234.8
−5
78,908.0
−4
76,655.3
−3
74,474.2
−2
72,362.1
−1
70,316.7
0
68,335.6
1
66,416.7
2
64,557.9
3
62,756.9
4
61,012.0
5
59,321.1
6
57,682.4
7
56,094.3
8
54,554.9
9
53,062.2
10
51,615.9
11
50,213.1
12
48,853.0
13
47,533.9
14
46,254.7
15
45,013.9
16
43,810.3
17
42,642.6
18
41,509.8
19
40,410.5
20
39,343.9
21
Fig. 18 — Space Temperature Sensor (P/N HH51BX001)
Temperature Sensor, and Supply-Air Temperature Sensor
TEMP
RESISTANCE
(Ohms)
(F)
(Ohms)
38,308.7
22
10,698.1
37,304.0
23
10,459.4
36,328.8
24
10,226.8
35,382.1
25
10,000.0
34,463.0
26
9,778.9
33,570.7
27
9,563.4
32,704.2
28
9,353.1
31,862.8
29
9,148.2
31,045.7
30
8,948.4
30,252.0
31
8,753.5
29,481.1
32
8,563.4
28,732.2
33
8,378.0
28,004.6
34
8,197.1
27,297.7
35
8,020.7
26,610.8
36
7,848.6
25,943.4
37
7,680.6
25,294.7
38
7,516.8
24,664.2
39
7,356.9
24,051.4
40
7,200.9
23,455.6
41
7,048.6
22,876.5
42
6,900.0
22,313.4
43
6,755.0
21,765.9
44
6,613.4
21,233.5
45
6,475.2
20,715.7
46
6,340.3
20,212.2
47
6,208.5
19,722.4
48
6,079.9
19,245.9
49
5,954.3
18,782.4
50
5,831.7
18,331.5
51
5,712.0
17,892.8
52
5,595.0
17,465.9
53
5,480.8
17,050.4
54
5,369.2
16,646.1
55
5,260.2
16,252.6
56
5,153.7
15,869.6
57
5,049.7
15,496.8
58
4,948.1
15,133.8
59
4,848.8
14,780.4
60
4,751.8
14,436.4
61
4,657.0
14,101.3
62
4,564.4
13,775.1
63
4,473.8
13,457.3
64
4,385.3
13,147.9
65
4,298.9
12,846.4
66
4,214.3
12,552.8
67
4,131.7
12,266.8
68
4,050.9
11,988.1
69
3,971.9
11,716.6
70
3,894.6
11,452.0
71
3,819.1
11,194.2
72
3,745.3
10,943.0
73
3,673.1
NEMA — National Electrical Manufacturers' Association
TEMP
RESISTANCE
(F)
(Ohms)
74
3602.5
75
3533.4
76
3465.9
77
3399.8
78
3335.2
79
3272.0
80
3210.1
81
3149.6
82
3090.4
83
3032.5
84
2975.8
85
2920.3
86
2866.0
87
2812.9
88
2760.9
89
2710.0
90
2660.2
91
2611.4
92
2563.7
93
2516.9
94
2471.2
95
2426.4
96
2382.5
97
2339.5
98
2297.5
99
2256.3
100
2215.9
101
2176.4
102
2137.7
103
2099.8
104
2062.6
105
2026.3
106
1990.6
107
1955.7
108
1921.5
109
1887.9
110
1855.1
111
1822.9
112
1791.3
113
1760.4
114
1730.1
115
1700.4
116
1671.3
117
1642.7
118
1614.7
119
1587.3
120
1560.4
121
1534.1
122
1508.2
123
1482.9
124
1458.0
125
1433.6
41
TEMP
RESISTANCE
TEMP
(F)
(Ohms)
(F)
126
1409.7
178
127
1386.3
179
128
1363.3
180
129
1340.7
181
130
1318.6
182
131
1296.9
183
132
1275.6
184
133
1254.8
185
134
1234.3
186
135
1214.2
187
136
1194.5
188
137
1175.1
189
138
1156.1
190
139
1137.5
191
140
1119.2
192
141
1101.3
193
142
1083.7
194
143
1066.4
195
144
1049.4
196
145
1032.8
197
146
1016.5
198
147
1000.4
199
148
984.7
200
149
969.2
201
150
954.0
202
151
939.1
203
152
924.5
204
153
910.1
205
154
896.0
206
155
882.2
207
156
868.6
208
157
855.2
209
158
842.1
210
159
829.2
211
160
816.6
212
161
804.1
213
162
791.9
214
163
779.9
215
164
768.2
216
165
756.6
217
166
745.2
218
167
734.0
219
168
723.1
220
169
712.3
221
170
701.7
222
171
691.3
223
172
681.0
224
173
671.0
225
174
661.1
226
175
651.4
227
176
641.8
228
177
632.4
229

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

39nx series

Table of Contents