Carrier 39HXC Installation, Operation And Maintenance Instructions

Carrier 39HXC Installation, Operation And Maintenance Instructions

Hide thumbs Also See for 39HXC:

Advertisement

Quick Links

I N S TA L L AT I O N , O P E R AT I O N A N D
M A I N T E N A N C E
I N S T R U C T I O N S
39HXC - 39HXE- 39HXEZ - 39HXV
Translation of the original document

Advertisement

Table of Contents
loading

Summary of Contents for Carrier 39HXC

  • Page 1 I N S TA L L AT I O N , O P E R AT I O N A N D M A I N T E N A N C E I N S T R U C T I O N S 39HXC - 39HXE- 39HXEZ - 39HXV Translation of the original document...
  • Page 2: Table Of Contents

    4.3 - TECHNICAL CHARACTERISTICS ............................11 5 - INSTALLATION AND INSTALLATION CONNECTIONS ......................16 5.1 - OUTDOOR INSTALLATION (39HXC, 39HXE and 39HXEZ models only) ................16 5.2 - 39 HXEZ 100 and 150: PROCEDURE FOR ROOF ASSEMBLY .................... 17 5.3  -  39HXEZ / Verification of pressures ............................30 5.4 ...
  • Page 3: Foreword

    1 - FOREWORD 1.1 - GENERAL INFORMATION Installation, start-up and maintenance operations for this equipment may be dangerous if certain factors particular to this installation,  such as the presence of electrical and live components and the installation location, are not taken into account. Only authorised, qualified installers and technicians, who have undergone specific training on the product in question, are permitted  to install and start up this equipment. During any servicing operations, all the recommendations and instructions given in the maintenance brochures, on the labels or in the  instructions accompanying the equipment must be observed, along with any other applicable safety instructions. - Observe all the regulations in the safety codes. - Wear safety goggles and working gloves - Handle heavy and bulky equipment with care when lifting, handling and setting down. During normal use, this unit is intended to operate under the following site conditions: - Maximum altitude: 1000 m, - Minimum and maximum temperatures: -10 °C + 40 °C, - Overvoltage category: III - Pollution degree: 3 1.2 - PROTECTION AGAINST ELECTROCUTION Only personnel qualified in accordance with the IEC (International Electrotechnical Commission) recommendations must be allowed  to access the electrical components. It is particularly recommended that all the electrical supplies to the unit are switched off before  any work is carried out. Cut the main power supply using the disconnect switch or circuit breaker. Important: the control system includes electronic components. These may cause or be subject to electromagnetic disturbance if they are not installed and used in accordance with these instructions.
  • Page 4: Receipt

    For your safety, we recommend the use of PPE (Personal Protective  Equipment) 2 - RECEIPT The installation and maintenance operations must be performed by qualified and experienced personnel. Follow the operating precautions to the letter when working on the unit. Labels have been placed on the unit to remind you of  the safety instructions. As a general rule, follow all applicable safety regulations and standards. Damage to the 39HX dual-flow air handling unit will be disregarded in case of failure to follow the instructions in this document. Each unit has a name plate bearing an identification number. This number must be quoted in all correspondence.  In accordance with Article 133-3 of the French Code of Commerce, the recipient is entirely responsible for checking the condition of  the goods received. In the event of missing items, the customer must provide the exact number of parcels delivered. Any damaged or  missing items must be specified on the delivery note in the presence of the driver before signing the delivery note. These comments  must be confirmed to the carrier by registered letter within 3 business days. The comments "conditional" and "pending unwrapping"  shall have no value. The customer must unwrap the goods in the presence of the driver. Claims must be made at the time of delivery  and be described in detail. The unit must be stored in its packaging and sheltered from weather. 39HXC, 39HXE, 39HXEZ and 39HXV • The 3 sizes of the 39HXV model and the size 1000 of the 39HXC, 39HXE and 39HXEZ models are packaged units, delivered  mounted on feet. • Sizes > 1000 for the 39HXC, 39HXE and 39HXEZ models are multi-block units, delivered assembled. The blocks can be split  in order to facilitate their passage through doorways (see splitting procedure in the HANDLING part). • Sizes 100 and 150 of the 39HXEZ model are delivered in 2 blocks. You are responsible for assembling these yourself on site.  Quick connectors enable the electrics for these blocks to be connected quickly and easily.
  • Page 5: Handling

    If  the  unit  is  handled  by  a  lifting  beam  +  slings,  tubes  need to be placed in the holes provided in the support feet. Ensure that the crane hook adapter is large enough to prevent  the belts applying any pressure to the AHU casing. Furthermore,  ensure that the steel tubes are secured to prevent any movement. If the above-mentioned lifting methods cannot be used, the unit  may be lifted using a forklift truck, taking great care not to dent  the lower panel (use forks of a sufficient length). Follow the applicable handling rules. 39HXC, 39HXE and 39HXEZ models Procedure for uncoupling 39HX multi-blocks or assembling the 2 blocks for the 39HXEZ 100 & 150 1  Remove the 4 nuts and screws Undo the screws on each beam and remove them.
  • Page 6 3 - HANDLING Disconnect the electrical connectors on the control and disconnect switch. 4  You can now separate the blocks. Note: Follow the procedure in reverse to re-couple the blocks, particularly for the 39HXEZ100 & 150. When uncoupling the blocks, ensure that the 18X10 PVC gasket located between the blocks remains correctly in place  to guarantee a perfect seal. If necessary, fit one. NB: if there is a roof, remove it first in accordance with the instructions given on the roof fitting plan (see technical specifications). 39HXC, 39HXE, 39HXEZ and 39HXV models These models are placed directly on a flat, smooth floor. The flatness value must be the best possible, around one per thousand.  Under normal conditions of use, there is no need to fix the unit to the floor. The  unit's  support  feet  must  be  standing  fully  on  their  contact  surface.  It is  important  to  allow  sufficient  service  space  to  facilitate  maintenance operations.
  • Page 7: Description Of The Unit & Technical Characteristics

    4 - DESCRIPTION OF THE UNIT & TECHNICAL CHARACTERISTICS 4.1 - DESCRIPTION OF THE UNIT Firm data plate Réf. Produit / Item Ref. Désignation / Description 7219278.405377 XXXXXXXXXXXXXXX An / Year N. Serie : Serial Nbr Composant / Composant Repère / Part 02380021/0001 CTA 22 FDY TENSION / VOLTAGE...
  • Page 8 1313 1758 1593 1901 1735 Additional box Correspondence with 39HX Dimensions of the additional Size of additional casing Weight of the additional box (kg) model 39HXC/HXE/HXEZ 010  589x400x810 39HXV 007 39HXC/HXE/HXEZ 020 689x400x1010 39HXV 015 & 020 39HXC/HXE/HXEZ 030 759x400x1210 39HXC/HXE/HXEZ 040 & 050 909x400x1510 39HXC/HXE/HXEZ 060 & 075 1059x400x1810 The dimensions in the tables above include all the components attached to the casing (hinges, collars, feet). ...
  • Page 9: Location Of Components

    4 - DESCRIPTION OF THE UNIT & TECHNICAL CHARACTERISTICS 4.2 - LOCATION OF COMPONENTS 39HXE 1  Fan motor assembly 2  General switch (on outer casing)  3  Controller electric box Depending on the unit configuration 3  Power electric box 4  Filter 5  Rotary heat exchanger 6  39HX Control display 7  Internal coil + valve mounting 8  Mixing option (damper + servomotor) 9   Purge sector on the wheel  10   Pressure connections P22 & P11 39HXEZ...
  • Page 10 4 - DESCRIPTION OF THE UNIT & TECHNICAL CHARACTERISTICS 39HXC 1  Fan motor assembly 2  Plate heat exchanger 3  Drain pan 4  General switch (on outer casing) 5  Electrics box (control and power) 6  Damper 7  Filters 39HXV 1  Fan motor assemblies 2  Plate heat exchanger 3  Filters 4  Power and controller electric box 5  Condensate drain 6  Condensate drain pan Coil 8  Valve assembly...
  • Page 11: Technical Characteristics

    4 - DESCRIPTION OF THE UNIT & TECHNICAL CHARACTERISTICS Additional coil box Coil 2  Valve assembly 4.3 - TECHNICAL CHARACTERISTICS Air flow rates 39HXC 39HXC Size Minimum flow rate (m³/h) Nominal flow rate (m³/h) Maximum flow rate (m³/h) 1000 1200 2000...
  • Page 12 Universal dimensions 287 x 592 x 48 39HXV filters Sizes Filter Dimensions x Number of cells/air flow (330x597x48) x1 (471x697x48) x1 (541x697x48) x1 Dual filtration When dual-stage filtration is installed, the two stages of cells are installed on the same runner. This assembly is available on the  39HXC, 39HXE, 39HXEZ and 39HXV models. Fan motor assembly EC motor This fan motor assembly is a direct coupling "Plug fan" with rotation speed  adjustment via the hand-held micro-terminal, or by automatic adaptation  to a given setpoint. The 39HX is equipped with 2 fan motor assemblies (1 at the intake and 1 at the exhaust), and there are 4  fan motor assemblies for sizes 100 & 150 of the 39HXE and 39HXEZ models 39HXC, 39HXE and 39HXEZ Sizes 040 &...
  • Page 13 4 - DESCRIPTION OF THE UNIT & TECHNICAL CHARACTERISTICS Heat recovery unit "Contra Flow" plate heat recovery unit (for the 39HXV model)  equipped with a condensate drain pan, a motorised by-pass and controlled  by the 39HX Control. Rotary  heat  exchanger  (39HXE  and  39HXEZ  model)  with variable speed, controlled by the 39HX Control. 39HXEZ model: equipped with a purge sector Options and accessories Support feet and accessories (39HXV, 39HXC, 39HXE & 39 HXEZ only) To obtain a greater clearance height, fit the adjustable feet (30 to 100 mm) underneath the standard feet. Reinforcement  plate Air flow Cylinder...
  • Page 14 4 - DESCRIPTION OF THE UNIT & TECHNICAL CHARACTERISTICS sensor The CO  sensor must be positioned on the return air duct, so that it can measure the CO  level emitted from the part(s) treated. This sensor is supplied as a spare part and the manual for this is included in its packaging. Operating principle sensor To configure the CO  level activation threshold, refer to the information on air quality for the town/city in which the AHU is installed.  concentration scale and the effects on humans: (Our CO  sensor has an operating range of 0 to 2000 ppm) concentration Effect on humans 380 - 480 ppm Normal atmospheric level 600 - 800 ppm Correct level for enclosed spaces 1000 - 1100 ppm Tolerable level for enclosed spaces 5000 ppm Upper limit for 8 hours of exposure  sensor (sensor in duct): refer to the attached supplier manual Duct pressure sensor The optional constant pressure mode is available in two versions - Constant pressure on intake: the air intake fan is controlled to maintain the supply air duct pressure. The extraction fan copies  the intake air flow. It is possible to create an offset between these two flow rates by configuring the M factor between 0.5 and 1.5 ...
  • Page 15 4 - DESCRIPTION OF THE UNIT & TECHNICAL CHARACTERISTICS To guarantee that the ducted pressure sensor operates correctly, it must be autozeroed before its system is started up.  To do this, power up the sensor, disconnect the tubing from the 2 pressure connections, marking their positions, and press the "Autozero"  button found inside the unit. Refit the two pressure tubes in their respective positions. This autozero should be checked once a year. Autozero button Changeover thermostat for mixed coil The customer is responsible for installation on the hydraulic system. The Changeover thermostat installed on the pipe must be integrated into the hydraulic pipe insulation Technical characteristics Min. WINTER temperature: 28 °C Min. SUMMER temperature: 18 °C Breaking capacity: 5(3) A. Cable length: 2500 mm Ø 1/2" or 7/8" BLACK wire (winter) IVORY wire (shared) BLUE wire (do not use) Damper The damper is not protected against the weather if the canopy option has not been selected. ...
  • Page 16: Installation And Installation Connections

    5 - INSTALLATION AND INSTALLATION CONNECTIONS The installation of the equipment must comply with the regulations and standards of the recipient country The additional box must be positioned in the duct so that the temperature sensor is on the downstream side (air supply) Special recommendations: • Connections must not place mechanical stresses on the unit. • Keep all inspection doors closed while the unit is operating • If fitted outdoors (39HXC, 39HXE and 39HXEZ models only), the units must be installed so as to withstand the climate conditions  in the installation location (risk of snow: height from ground/risk of wind: suitable fixings, swan-neck type electrical connection  to the unit, etc.). Flexible sleeve Ensure all electrical components are earthed.  5.1 - OUTDOOR INSTALLATION (39HXC, 39HXE and 39HXEZ models only) The installation of a 39HX dual-flow unit outdoors requires a roof and a canopy to be fitted; these are usually supplied mounted* and  adapted to suit each configuration. (* Supplied in kit form if delivery of the elements assembled is not possible) Fitting the roofs: The roofs of 39HX units are designed to provide sufficient protection against adverse weather conditions, as they overlap the edge of  the unit by 80 mm. Fitting procedure: 1  Fix the foam seal along the length of the unit. (50 x 20 foam seal). 2  Fix the roof panel(s) along the entire length of the unit. 50x20 foam gasket bonded for roof ...
  • Page 17: 39 Hxez 100 And 150: Procedure For Roof Assembly

    5 - INSTALLATION AND INSTALLATION CONNECTIONS 5.2 - 39 HXEZ 100 and 150: PROCEDURE FOR ROOF ASSEMBLY ■ The 39HXEZ 100 & 150 are delivered in two blocks: a Wheel Block & an FMA Block, with a roof attached to each block ■ Procedure for assembling the roof  1.  Remove the roof from the Wheel block (retaining the screw and cap) 2.  Assemble the blocks 3.  Reposition the roof from the Wheel Block, taking care to ensure the roofs interleave correctly 4.  Secure the roof to the block Delivery of two separate blocks: WHEEL Block + FMA Block Removal of the WHEEL Block roof ...
  • Page 18 5 - INSTALLATION AND INSTALLATION CONNECTIONS Removal of the WHEEL Block roof  Refitting of the WHEEL Block roof ...
  • Page 19 5 - INSTALLATION AND INSTALLATION CONNECTIONS Assembly of the two Blocks with their roofs...
  • Page 20 5 - INSTALLATION AND INSTALLATION CONNECTIONS Assembling the canopy: The upper panel will be assembled on the two side panels using screws, washers and nuts or sealed rivets. Also fit the protective screen  during assembly, either on the damper or on the panel, as applicable (see illustrations) Canopy with damper Canopy without damper Sealed rivet Screen Screen Screen M x F 39HXE and 39HXEZ N x E M x F Weight (kg) 329.5 2X135 750,5 2X185  1189 1152 2X260 3X340 040 / 050 1489 1452 2X305...
  • Page 21 5 - INSTALLATION AND INSTALLATION CONNECTIONS Flexible sleeve: COMPOSITION of a flexible sleeve package:  - 1 sewn sleeve casing - 8 strips to be assembled (4 widthways + 4 lengthways) 1  Insert the strips into the hems of the sleeve, checking to ensure the holes are aligned: 2  Assemble the strips together, first identifying the two lengthways strips and the two widthways strips. Fit them together and strike  in turn to seat / Proceed in the same manner for the two sides of the sleeve: 3  Fitting on the machine with screws and washers:...
  • Page 22 5 - INSTALLATION AND INSTALLATION CONNECTIONS CONNECTIONS DIMENSIONS OF AIR FLOW CIRCUITS 39HXC, 39HXE and 39HXEZ Sizes 040 / 050 060 / 075 Connections (mm) 201x502 301x601 458x984 608x1284 758x1584 797x1577 807x1907 air intake and discharge* * Internal dimensions 39HXV Sizes Air inlet...
  • Page 23 5 - INSTALLATION AND INSTALLATION CONNECTIONS The diameter of the condensate tube on all the pans is 16 mm 39HXC, 39HXE and 39HXEZ Sizes 2 rows 2 rows Inlet G 1/2" G 1/2" G 3/4" G 3/4" G 3/4" G 1" G 1" G 1"1/2 G 1"1/2 Ø connections (mm) 4-way valve Outlet (on valve) G 1/2" G 1/2" G 3/4" G 3/4" G 3/4" G 1"1/2 G 1"1/2...
  • Page 24 5 - INSTALLATION AND INSTALLATION CONNECTIONS Additional electrical heater box Sizes 39HXC/HXE/ 39HXC/HXE/ 39HXC/HXE/ 39HXC/HXE/ 39HXC/HXE/ 39HXC/HXE/ 39HXC/HXE/ HXEZ 010 39HXV 015 HXEZ 2000 Associated model HXEZ 030 HXEZ 040 HXEZ 050 HXEZ 060 HXEZ 075 39HXV 007 39HXV 020 230 V 1-Ph...
  • Page 25 5 - INSTALLATION AND INSTALLATION CONNECTIONS Marking of the options terminal strip for the 39HXE, 39HXEZ, 39HXC and 39HXV models. Wire references AHU operating feedback Danger fault return Common fault return Maintenance fault return Setpoint 1/Setpoint 2 selection Remote control 24V supply air/return air dampers control 24V fresh air/exit air dampers control Intake duct pressure sensor or air quality  sensor 0 -10V valve 1 control 0 -10V valve 2 control Valves 24V supply Changeover thermostat Intake air duct temperature  sensor Pump 1 monitoring Pump 2 monitoring Pump 1 control Pump 2 control...
  • Page 26 5 - INSTALLATION AND INSTALLATION CONNECTIONS Additional box terminal block references Hydraulic coil valve control Remote temperature sensor Electric heater safety monitoring Electric heater stage 2 control Electric heater stage 1 control Electric heaters Pre-heats 1 stage: 4 wires Machine terminal block Additional box terminal block Notes Inlet/Outlet Xm 22 _ b-3 Xm 7 _ b-1 On/off control Digital outputs 24 VAC Xm 22 _ b-4 Xm 7 _ b-2 Xm 22 _ b-7 Xm 7 _ b-4 Electric heater safety thermostat return...
  • Page 27 5 - INSTALLATION AND INSTALLATION CONNECTIONS Pre-heating 1 stage + post-heating 1 stage: 4 + 6 wires Additional box terminal block Machine terminal Additional box terminal block Notes Inlet/Outlet block Post-heating Pre-heating Xm 22 _ b-1 Xm 7 _ b-1 Post-heating ON/OFF control  (24 VAC) Xm 22 _ b-2 Xm 7 _ b-2 Digital outputs Xm 22 _ b-3 Xm 7 _ b-1 Pre-heating ON/OFF control ...
  • Page 28 Dry contact Xm 22 _ b-10 Contact normally closed AHU operating feedback Machine terminal block Notes Inlet/Outlet Xm 18 _ b-1 AHU operating feedback Digital output Dry contact Xm 18 _ b-2 Pump 1 monitoring: 4 wires Machine terminal block Notes Inlet/Outlet Xm 21 _ b-5 ON command Pump 1 Digital inputs 24 VAC Xm 21 _ b-6 Xm 21 _ b-1 Pump 1 fault monitoring Digital inputs Dry contact Xm 21 _ b-2 Pump 1 ON command if Hydraulic coil 1 operating order As Xm21 B5-6 is 24 VAC polarised on the Pump1 ON command, provide a 24 VAC relay (50/60 Hz, max 0.75 VA; not supplied by  CARRIER)
  • Page 29 Inlet/Outlet Xm 21 _ b-7 ON command Pump 2 Digital inputs 24 VAC Xm 21 _ b-8 Xm 21 _ b-3 Pump 2 fault monitoring Digital inputs Dry contact Xm 21 _ b-4 Pump 2 ON command if Hydraulic coil 2 operating order As Xm21 B7-8 is 24 VAC polarised on the Pump2 ON command, provide a 24 VAC relay (50/60 Hz, max 0.75 VA; not supplied by  CARRIER) Remote On/Off: 2 wires Machine terminal block Notes Inlet/Outlet Xm 18 _ b-8 Unit ON/OFF monitoring Digital inputs Dry contact Xm 18 _ b-9 Setpoint 1/setpoint 2 selection: 2 wires Machine terminal block Notes Inlet/Outlet Xm 18 _ b-6...
  • Page 30: 39Hxez / Verification Of Pressures

    5 - INSTALLATION AND INSTALLATION CONNECTIONS Assembly with depression : Z: X+Y+tubing diameter + insulation thickness Y: Y = 0.5 * X X: X = 25 mm for each 250 Pa of negative static pressure + 25 mm  Negative pressure recovery  mmWC Slight slope of  0.005 To sewer  system Assembly with pressure: X = 12 mm Y = 12 mm + total static pressure (1 mm for 10 Pa) NOTE: The condensate pan on the heat recovery unit is pressurised on the 39HXV model, and is also pressurised if there is a cooling  or mixed coil in the additional box. 5.3 - 39HXEZ / Verification of pressures Verification of the pressures for EATR limitation: - The limitation of the EATR value depends on the size of the installation and, specifically, the pressure drop on the exhaust air duct ...
  • Page 31: Maintenance / Space In Front Of The Units

    5 - INSTALLATION AND INSTALLATION CONNECTIONS - This translates as ΔP22-11 > 0  (for example: P22 = -300 Pa → P11 = -350 Pa)  - Ideally, the minimum value between P22 and P11 should be 20 Pa - The pressure should be lower at P11 as per the above; if not the case, adjust the damper or dampers present in the return air  duct 5.4 - Maintenance / Space in front of the units Ideally, for all simple and complex maintenance work (removal of the exchanger, coils, etc.),  sufficient free space should be left at the front to perform these operations: L = machine length  H = operator height for small models / machine height for Sizes > 6000 040/050 060/075 1100 1400 1700 1800 2100...
  • Page 32: System Start-Up

    6 - SYSTEM START-UP Commissioning must be performed by qualified personnel, trained in air handling technology. Keep all inspection doors closed while the unit is operating. Once the electrical and hydraulic connections have been carried out, proceed with the system start-up of the unit, checking the steps  below: - Check the tightness of all connections, - Make sure that the inside of the unit is clean, and that there are no foreign bodies inside it, - Check the wiring - Check the electrical supply voltage and the ratings of the overload protections against the current ratings of each component, - To configure the setpoints, refer to the corresponding manual (N09.61), - Simulate activation of the various electric components, controlled components and alarms, - Check the currents: •...
  • Page 33: Maintenance/Service Intervals

    Switch off the electrical supply to the air handling unit before carrying out any work Details of hinges/handles: Allen key locks, size 4 When they are unlocked, the handles are in "hinge" mode. It is possible to unlock a single row of handles to open like a conventional  door. If all of the handles are unlocked, the door can be removed. Handle locked Handle unlocked Door 7.1 - FILTERS After commissioning, the speed of filter fouling will depend on the care taken when cleaning the air flow circuits. Hence the frequency  of filter checks should be increased during this period. Maintenance intervals The filter life depends essentially on the amount of dust in the air and the efficiency of the filtration system. The filtration quality cannot  be maintained if the filter medium has been damaged during maintenance. We recommend that the filters be replaced once every two  years, even in the case of moderate use Filter replacement method During filter maintenance operations, it is important not to spread the dust that has accumulated in the filters.  Shut down the unit, Access the filters by opening the door panels, Simply pull on the filters  Pull out the slide-type terminal (present on the 39HXC, 39HXE & 39HXEZ models ≥ 3000 m3/h); the filters can then be removed. For  the other models, simply pull directly on the filters. Example: 39HXC Slide-type terminal Filter...
  • Page 34: Fan Motor Assembly

    7.2 - FAN MOTOR ASSEMBLY Check and retighten the electrical connections once a year. Removing the fan Open the door as explained above,  Unlock the 4 x M8 screws using the ratchet wrench and its extension, Disconnect the motor's electrical connections, Remove the fan via the access door. Example: 39HXC 7.3 - HEAT RECOVERY UNIT Plate heat exchangers (39HXV and 39HXC models) Schedule annual dust removal / degreasing and maintenance of the bypass damper. It is important to remember to clean and degrease the condensate drain pan using water and non-abrasive detergents:  The heat recovery unit on the 39HXV model is accessible via the door and can be removed on the slide-type terminal. Rotary heat exchangers (39HXE and 39HXEZ model) Check the maximum and minimum rotation speeds once a year. When stationary, the rotary heat exchangers accumulate dust and moisture  at their lowest point. Schedule cleaning during prolonged stoppages.  Check the permanently lubricated bearings once a year.
  • Page 35: Electric Heaters

    Filters Replace replace if necessary Fans Check the connections Retighten the connections Retighten the electrical  connections Electrics box Check the connections Operating check Check the components Operating check Check correct operation  Check correct operation and  Check correct operation and  Pressure/temperature sensor and setpoint adjustment setpoint adjustment setpoint adjustment Clean with water and a  Clean with water and a  Condensate pan non-abrasive detergent non-abrasive detergent 9 - TESTS AND GUARANTEES To guarantee the product's quality, each 39HX air handling unit undergoes a variety of tests: EMC (electromagnetic compatibility) test,  component functional tests (fan motor assembly, heat recovery unit, sensor, etc.). However, our units are guaranteed for a period of 12 months from the commissioning date, when this date occurs within three months  of the invoice date.  It is effective for a period of 15 months from the unit invoice date in all other cases. CIAT's guarantee on motors is limited to the terms of guarantee extended by its supplier.  Under no circumstances must the fitter carry out work on the motor. This will invalidate any future claims on the warranty. Note: for further information, refer to the application of the Carrier warranty.
  • Page 36 CARRIER participates in the ECP programme for LCP/HP Check ongoing validity of certificate: www.eurovent-certification.com Order No: EN7565707-01, 11.2020. Supersedes order No.: EN7565707-00, 05.2019. Manufacturer: CIAT SAS, Culoz, France. The manufacturer reserves the right to make changes to the product specifications without notice.

This manual is also suitable for:

39hxe39hxez39hxv

Table of Contents