Carrier 39LA Installation, Start-Up And Service Instructions Manual page 32

Indoor air-handling units
Table of Contents

Advertisement

Fig. 38 — Horizontal Unit Slant Coil Removal (39LA Units — Sizes 03-21)
VERTICAL UNIT SLANT COIL REMOVAL (39LD
Units)
NOTE: Item numbers are in Fig. 39.
1. Refer to Fig. 4 for service area clearance.
2. Disconnect piping (Item 6).
3. Through fan access door (Item 2), remove screws
(Item 3), while holding angle (Item 4) to top of coil side
panels (Item 7). On opposite end of unit, gain access to
similar screws by removing side panels (Item 1).
4. Remove right side panels (Item 7).
NOTE: Support of fan section may be required after re-
moval of side panels (Items 7 and 16).
5. If accessory is present, remove accessory side panel
(Item 15) on left side of unit. Detach filter track support
bracket if upstream accessory is a filter.
1 — Accessory Side Panel
2 — Left Side Panel
3 — Top Panels
4 — Baffle Screws
5 — Piping
6 — Right Side Panels
7 — Right Support Panel
LEGEND
8 — Condensate Baffle
9 — Holddown Screws
10 — Coil
11 — Holddown Screws
12 — Left Support Panel
13 — Inside Baffle
6. Remove screws from inside baffle (item 14). Leave baffle
attached to left side panel (Item 16).
7. Remove left side panel (Item 16).
NOTE: Support of fan section may be required after re-
moval of side panels (Items 7 and 16).
8. Remove condensate baffle (Item 9).
9. Remove coil holddown screws (Items 10 and 12).
10. Remove baffle screws (Item 5) from downstream side of
coil.
11. Tilt coil (Item 11) away from coil support panels (Items 8
and 13).
12. Replace coil by reversing preceding Steps 1 - 11.
32