Diagnosis
(cont.)
Fault code System character-
istics
2A
Burner control unit
fault
2b
Burner control unit
fault
2C
Burner control unit
fault
2d
Burner control unit
fault
2E
Burner control unit
fault
2F
Burner control unit
fault
2H
Burner control unit
fault
31
Burner control unit
fault
32
Burner control unit
fault
35
Burner control unit
fault
36
Fan speed during
start up or during
operation is outside
the set range for
longer than 5 s; the
speed for ignition
setting or start up
output in operation
is not reached
Cause
Remedy
Internal fault of
Replace the burner con-
the gas pressure
trol unit.
switch input
Internal flame
Replace the burner con-
monitor fault
trol unit.
Fault during test
Replace the burner con-
of safety inputs
trol unit.
Internal low vol-
Replace the burner con-
tage monitor fault
trol unit.
Internal voltage
Replace the burner con-
failure monitor
trol unit
fault
Internal heat de-
Replace the burner con-
mand fault
trol unit.
Strapping plug
Check the strapping
break fJ safety
plug fJ.
chain
Error in feedback
Replace the burner con-
from gas safety
trol unit.
valves, output
relay does not re-
spond
Error in feedback
Replace the burner con-
from auxiliary
trol unit.
start up valve,
output relay does
not respond
Error in feedback
Replace the burner con-
from ignition, out-
trol unit.
put relay does not
respond
The fan is faulty;
Check the cables and
cable "100a" is
replace cable "100a" or
faulty or broken
the fan, if required.
Troubleshooting
43