Start-Up; Service; Fan Motor Lubrication; Fan Shaft Bearings - Carrier 40RM Installation, Start-Up And Service Instructions Manual

Packaged air-handling units 50/60 hz
Hide thumbs Also See for 40RM:
Table of Contents

Advertisement

START-UP

Before starting unit, check the following and correct as
necessary:
• Is unit solidly supported?
• Is fan adjusted for speed and pulley alignment?
• Are pulleys, motor, and bearings securely mounted?
• Are there any loose parts that will rattle or vibrate?
• Is condensate drain pan pitched for correct drainage?
• Are coil baffle plates tight against coil to prevent air
bypass?
• Are all panels securely fastened?
• Are all electrical connections correct and tight?
Also refer to condensing unit instructions before starting
a split system. A split system start-up checklist is provided
in the back of these instructions.

SERVICE

Inspection and maintenance should be performed at
regular intervals and should include the following:
• Complete cleaning of cabinet, fan wheel, cooling coil, con-
densate pan and drain, heating coils, and return-air grille
(if present).
• Inspection of panels and sealing of unit against air
leakage.
• Adjustment of fan motor, belt, bearings, and wheels.
• Cleaning or replacement of filters.
• Testing for cooling/heating system leaks.
• Checking of all electrical connections.
Most unit service can be performed by removing one or
both of the unit's side panels. Coil cleaning or removal or
insulation cleaning may require removal of a rear, top, or
bottom panel, depending on the unit's orientation. When serv-
ice is completed, replace unit panels.
Panels —
Panels are fastened to unit frame with sheet
metal screws. Fan and coil compartment must be sealed tightly
after service to prevent air from bypassing the cooling coil.
Fig. 16 — Duct Flange Installation
Fan Motor Lubrication —
unit is permanently lubricated and requires no further
lubrication.
Fan Shaft Bearings —
are sealed, permanently lubricated bearings that require no
further lubrication. Size 014-034 units have pillow-block bear-
ings (Fig. 17) that must be lubricated with suitable bearing
grease approximately every 3 months. See Table 7 for suit-
able lubricants.
*Preferred lubricant because it contains rust and oxidation
inhibitors.
23
Bearings on 007-012 size units
Table 7 — Lubricant Data
MANUFACTURER
Sunoco
Texaco
Texaco
Mobil
Fig. 17 — Fan Shaft, Bearings, and Fan Wheel
(Typical)
Fan motor supplied with
LUBRICANT
Prestige 42
Multifak 2
Regal AFB-2*
Mobilplex EP No. 2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

40rms40rmq

Table of Contents

Save Article as PDF