Daikin FTXS-L Series Engineering Data page 70

Hide thumbs Also See for FTXS-L Series:
Table of Contents

Advertisement

EDUS091128
3.
How to set the different addresses
system
4.
When connecting to an HA system
(wired remote controller, central remote controller etc.)
Screw
3) Remove the metal plate
electrical wiring cover.
Refrigerant Piping Work
1.
Flaring the pipe end
WARNING
Split Type Air Conditioners FTXS-L / FDXS-L Series
When connecting to an HA
Pull
Pull
Slide
Tab
Slide
Metal plate
electrical cover
Main body
JA
JA
ADDRESS
EXIST
1
CUT
2
Tab
HA connector
(S21)
4) Attach the connection cord
to the S21 connector and
pull the harness out through
the notched part in the
(Cut exactly at
right angles.)
Remove burrs.
Set exactly at the position shown below.
A
Flare tool for R410A
Clutch-type
A 0-0.020 inch (0-0.5mm)
Die
Installation Manual
Jumper
ADDRESS:JA
EXIST
1
CUT
2
HA connector
(S21)
Lay the HA cord as
5) Replace the electrical
wiring cover as it was,
and pull the harness
around, as shown in
Check
The pipe end must
Flare's inner surface
perfect circle.
Make sure that the
Flaring
Clutch-type (Rigid-type)
Wing-nut type (Imperial-type)
0.039-0.059 inch (1.0-1.5mm)
0.059-0.079 inch (1.5-2.0mm)
69