SEcTION 2: cIRcuIT REQuIREMENTS

Operation

Serious personal injury could occur if you
connect the machine to power before com-
pleting the setup process. DO NOT connect
the machine to the power until instructed
later in this manual.
Electrocution or fire could
result if machine is not
grounded and installed in
compliance with electrical
codes. compliance MuST
be verified by a qualified
electrician!
full Load Amperage Draw Draw
g0605X @ 220v .................................. 23 amps
g0606X @ 220v .................................. 19 amps
g0606X @ 440v* ................................. 10 amps
circuit Requirements
you must connect your machine to a grounded
circuit that is rated for the amperage given below.
never replace a circuit breaker on an existing cir-
cuit with one of higher amperage without consult-
ing a qualified electrician to ensure compliance
with wiring codes. If you are unsure about the
wiring codes in your area or you plan to con-
nect your machine to a shared circuit, consult
a qualified electrician.
g0605X @ 220v .................................. 30 amps
g0605X @ 220v .................................. 30 amps
g0606X @ 440v .................................. 15 amps
-12-
power connection Device
the power connection device depends on the
type of installed or planned service. We recom-
mend using one of the devices shown in figure
2, depending on the voltage being used.
g0605X @220v single-phase .................. l6-30
g0606X @220v 3-phase .........................l15-30
g0606X @440v 3-phs ..........hardwired locking
disconnect switch
For 440v connections, an electrician must
hardwire the machine (using a metal conduit
setup) directly to a locking disconnect switch,
which is directly connected to the power source.
figure 2. recommended connection types.
model g0605X/g0606X (mfg. since 11/06)
l6-30
plug & outlet
for 220v, single-
phase
l15-30
plug & outlet
for 220v, 3-phase
hardwired locking
disconnect switch
for 440v, 3-phase