VIESMANN Installation and service instructions for contractors Vitogate 200 Type KNX Communication for heating systems via KNX/EIB systems VITOGATE 200 Please keep safe. 5673180 GB 5/2019...
Page 2
Prior to commencing work, touch earthed lidate our warranty. objects such as heating or water pipes, to dis- For replacements, use only original spare parts charge static loads. supplied or approved by Viessmann.
Page 3
Safety instructions Safety instructions (cont.) Safety instructions for operating the system If you smell flue gas Danger Leaking or blocked flue systems, or an inade- Danger quate supply of combustion air can cause life Flue gas can lead to life threatening poisoning. threatening poisoning from carbon monoxide in ■...
Protection against unauthorised access ..........Product information ................Functions ....................Spare parts lists ..................Installation sequence Installing the Vitogate 200, type KNX ............ Removing the cover ................■ Overview of connections ................ Connecting the Vitogate 200, type KNX ..........Connecting the power supply ..............10 Applying strain relief to all cables ............
Only use the specified may only be used in systems with supported components for the power supply (e.g. power supply Viessmann heat and power generators. units). The Vitogate can only be used with the user and com-...
To do this, set up VPN access, for example. Product information The following appliances are hooked up to KNX/EIB The Vitogate 200, type KNX must be integrated into systems with the Vitogate 200, type KNX gateway: the KNX/EIB system by an authorised contractor.
Installation sequence Installing the Vitogate 200, type KNX Please note Note Unfavourable ambient conditions can lead to When selecting the installation location, bear in mind malfunctions and appliance damage. the length of the connecting cables in the standard ■ The installation location must be dry and free delivery.
Installation sequence Installing the Vitogate 200, type KNX (cont.) Removing the cover Please note When the power supply is connected, touching electrical contacts can result in appliance dam- age. Always unplug the power supply unit before removing the cover. Fig. 2 Overview of connections Fig.
Ethernet connecting cable (KNXnet/IP) Note The Vitogate 200 has an integral terminator (con- nection "9"), so integrate the Vitogate 200 as the first or last LON subscriber. 2. Connecting the KNX TP cable Please note If the core assignment is incorrect, data exchange will not take place.
"1". do not match the power consumption of the Vito- gate, this can lead to interruption of operations 2. Close the Vitogate 200, type KNX. and damage to the power supply unit or the Vitogate.
Commissioning Display and operating elements With cover For the meaning of LEDs "2", "3" and "4", see the fol- lowing table "Display elements". Fig. 7 Without cover To remove the cover, see page 8. Fig. 8 "1" to "4" LEDs; for meaning see the following table "Display elements"...
Programming the physical KNX TP address for manual integration of the Vitogate 200, type KNX into an existing KNX/EIB system "T3" LON service for manual integration of the Vitogate 200, type KNX into an existing LON "T4" Software reset: Vitogate is re-started.
Vitogate 200, type KNX is only detected by the fault manager which has the same system number as the Vitogate 200, type KNX. The up to 4 other fault managers will not detect the Vitogate 200, type KNX.
After importing the device data into the Vitogate 200, the data points in the relevant KNX DPTs (KNX data point types) are available for setting parameters with the ETS.
Troubleshooting LON connection error If a LON subscriber (e.g. Vitotronic control unit) fails, The KNX/EIB system can display a corresponding no further data from this subscriber will be transferred error message if the data point error message has to the KNX/EIB system. been assigned for this LON subscriber.
Specification Vitogate 200, type KNX Operating voltage – Rated current 400 mA Protection class IP rating IP 30 to EN 60 529 Permiss. ambient temperature Operation +5 to +55 °C ■ Installation in living spaces or boiler rooms (standard ambient conditions) Storage and transport 20 to +60 °C...
Certificates Declaration of conformity We, Viessmann Werke GmbH & Co. KG, D-35107 Allendorf, declare as sole responsible body that the named product complies with the European directives and supplementary national requirements in terms of its design and operational characteristics. Using the serial number, the full Declaration of Con- formity can be found on the following website: www.viessmann.co.uk/eu-conformity...
Page 18
Keyword index Keyword index Ambient temperatures..........7 – Cable connection............9 – Cable length.............. 7 Button.................12 – Codes..............13 – Communication module.......... 12 – Connection, checking..........13 Cable length..............7 – Connection error............. 15 Cables, applying strain relief........10 – Control unit, integrating........... 12 Closing...............