Viessmann VITOCAL 242-S Installation And Service Instructions Manual page 147

Compact heat pumps, split version for heating and cooling operation
Hide thumbs Also See for VITOCAL 242-S:
Table of Contents

Advertisement

Specification
(cont.)
Type AWT-AC
Internal unit electrical val-
ues
Heat pump control unit/PCB
■ Rated voltage, control
unit/PCB
■ Fuse protection, power
supply
■ Internal fuse
Instantaneous heating water
heater
■ Rated voltage
■ Heating output
■ Fuse protection, power
supply
Electrical power con-
sumption
■ Fan (max.)
■ External unit (max.)
■ Secondary pump (PWM)
■ Control unit/PCB, external
unit (max.)
■ Control unit/PCB, internal
unit (max.)
■ Max. rating, control unit/
PCB
Refrigerant circuit
Refrigerant
Refrigerant charge
Top-up amount for line
lengths > 12 m to ≤ 30 m
Compressor (hermetically
sealed)
Permiss. operating pressure
■ High pressure side
■ Low pressure side
241.A04
241.A07
kW
W
65
kW
3.0
W
3 to 50
W
150
W
5
W
1000
R410A
kg
1.2
g/m
20
Type
Rotating
Rotating
piston
piston
bar
43
MPa
4.3
bar
43
MPa
4.3
241.A10
1/N/PE 230 V/50 Hz
1 x B16A
6.3 A (slow)/250 V
1/N/PE 230 V/50 Hz
3/N/PE 400 V/50 Hz
8.8
3 x B16A
70
130
3.6
4.6
3 to 50
3 to 70
150
150
5
5
1000
1000
R410A
R410A
2.15
2.95
60
60
Scroll
43
43
4.3
4.3
43
43
4.3
4.3
Specification
241.A13
130
5.8
3 to 70
150
5
1000
R410A
2.95
60
Scroll
43
4.3
43
4.3
147

Advertisement

Table of Contents
loading

Table of Contents