For strong wind installation place refer to the classification of the area according to the Beaufort table. If the value is > 7
(strong wind, average wind speed = 13,9-17,1 m/s) it is strictly necessary to keep the fan always powered, thus preventing
involuntary rotation of the same.
In the event of side-by-side units, the minimum Lmin distance be-
tween them is 2200 m.
Covering with canopies or placing near plants or walls should be avoid-
ed to prevent air circulation.
In the event of winds stronger then 13,9-17,1 m/s the use of wind
barriers is recommended.
We always invite you to make an environmental impact assessment based on the power and sound pressure data shown in chapter "Technical
data" and the sound emission limits based on the installation area of the unit , with reference to the DPCM of 14/11/1997. An assessment must
also be made if the unit is installed in the proximity of workers according to D. LGS. 81/2008 Art. 189 and following.
Picco R32
Model
A1
Picco R32 - 140
mm
1200
Picco R32 - 250
mm
1200
/ 260 / 270
Inverter air/water heat pumps with axial fan
A2
B1
1000
1000
1500
1000
1500
1500
L min
B2
13