Connecting The Flue Pipe; Start-Up; Carrying Out The Initial Start-Up; Checking And, If Required, Setting The Water Flow Rate - Vaillant atmoMAG MAG mini 114/1 I Installation And Maintenance Instructions Manual

Table of Contents

Advertisement

5.6

Connecting the flue pipe

Use a flue pipe with the diameter that is specified in the
technical data to connect the product to a flue system
that has a natural draught (chimney).
Insert the flue pipe (1) into the flue pipe connection (2) on
the down-draught diverter.
6

Start-up

6.1

Carrying out the initial start-up

Initial start-up must be carried out by a customer service
technician or a qualified competent person.
Remove the product casing (→ Page 9).
When starting up the unit, proceed in accordance with
the attached checklist.
Commissioning checklist (→ Page 20)
6.2
Checking and, if required, setting the water
flow rate
1.
Measure the water flow rate and compare the value
with the value specified in the technical data.
At initial start-up
After replacing the micro switch
0020273765_00 atmoMAG Installation and maintenance instructions
1
2
2.
If the measured value exceeds the value specified in
the technical data, set the flow rate at the micro switch
(1).
Clockwise rotation: Increase the starting flow rate
Anti-clockwise rotation: Decrease the starting flow
rate
6.3

Gas conversion

If the product is installed in a mobile home, it must not be
converted to a different gas type (using a conversion set)
other than the one specified on the data plate.
Leave the product in the gas type setting that was set at
the factory.
6.4
Gas conversion
1.
Observe the applicable national regulations.
2.
To convert the gas, use only Vaillant conversion sets or
Vaillant spare parts.
3.
Follow the instructions contained in the documentation
that is supplied with the conversion sets or spare parts.
Conditions: Installation in a mobile home
You must not convert the product to a gas type other
than the one that is specified on the data plate.
Leave the product in the gas type setting that was set at
the factory.
6.5
Checking that the flue gas sensor works
correctly
If the flue system is fully or partially blocked or the local air
pressure conditions restrict the smooth flue system, the flue
gas sensor registers an increase in temperature and inter-
rupts the gas supply.
Check that the flue gas sensor is working correctly, as de-
scribed below.
Start-up 6