HP MCS Front Doors

The MCS front door ships standard with every MCS unit. The MCS includes a front door with a
polycarbonite insert, which prevents chilled air from being re-circulated into the data center.

HP MCS Rear Doors

The MCS ships with solid rear doors as the standard configuration.

HP Side Panel Kit

Side panels ship as the standard configuration. Side panels aid in providing proper front to rear
airflow and a first level of security.
Important:
The MCS unit is not bayable and for proper air flow, the side panels should
not be removed from a MCS unit.

Stabilization for seismic activity

HP MCS installations in geographical areas where there is a risk of seismic activity require special
considerations for stabilization of the HP MCS.
Important:
The HP MCS is not a Zone 4 or OSHPOD solution.
An equipment integrator will need to determine the requirements for which, if any, ballast and
stabilizer kits are required. If the HP MCS is bolted to the floor or to an adjacent HP MCS that has
sufficient combined weight, additional stabilization products may not be required.

Space and cable management requirements

Important:
Roof-mounted fan kits should not be used in the HP MCS. The roof-mounted
fans are not compatible with the HP MCS air flow requirements.

Extension kits

Cables and equipment can be damaged in use or in shipping if there is insufficient room in the HP
MCS. Extensions can be used when additional room is required at the rear of the HP MCS to provide
adequate room for equipment and associated cables. The extension kit provides approximately 6.0
inches (155 mm) of additional space at the rear of the HP MCS.