Product Components; Mcs Specifications - HP MCS Manual

Modular cooling system
Table of Contents

Advertisement

Product components

Table 2 lists the key components of the HP MCS.
Table 2. HP MCS key components
Component
Description
Fan Module
A module containing one of the main, internal circulation fans. There are three hot-pluggable and
online serviceable fan modules within the HP MCS
Heat Exchanger
An air-to-water heat transfer device is designed for demanding data center
Module
environments and is the key component within the heat exchanger (hex) unit. There are
three hot-pluggable and online serviceable hex units within each HP MCS.
Patch Panel
The patch panel provides for connection of the AC power and network interfaces.
Water Group
A module containing the magnetic valve, flow meter, check valve and condensate
pump. There is one water group in each HP MCS.
Management
The Management Module provides users with web-based capabilities to set, monitor
Module
and control temperature and other parameters within the modular cooling unit, as well
as displays the health of the unit.
An Automatic Door Release Kit is included as standard with every MCS. The
Automatic Door
kit ships in the accessories box and is to be field-installed. The Automatic Door
Release Kit
Release Kit is designed to swing the MCS front and rear doors open in the case
of a sudden increase in the temperature inside the MCS. The open doors will
allow the IT equipment to cool using the air from the datacenter.

MCS Specifications

Table 3 lists HP MCS specification details.
Table 3. HP MCS specifications
Detail
Voltage
Height (including the rack)
Width (including the rack)
Depth (including the rack and rack handle)
Weight (including the empty rack)
Weight (gross with packaging)
Effective cooling with 25 I/minimum water
supply at 0º C, cold air at 25º C
Rated current maximum
Cooling medium
Minimum recommended water inlet temperature
Permissible operating pressure (maximum)
.
HP MCS specification
208–230 VAC +/- 10%, 50–60 Hz
200.7 cm (79 in.)
91.2 cm (35.9 in.) maximum
127 cm (50 in.)
512.6 kg (1130 lbs.)
557.2 kg (1230 lbs.)
35 kW
208 VAC–15 Amps
Water
7º C (45º F)
100 pounds-per-square-inch (psi)
3

Advertisement