Oil Pump Wiring; Figure 11 - Oil Pump Connections; Table 4 - Control And Oil Pump Wire Numbers And Termination Points For Yk Chiller; Table 5 - Control And Oil Pump Wire Numbers And Termination Points For Yd-Sys 1 And Yd-Sys 2 - York YK Installation Manual

Medium voltage 500 hp to 2500 hp, 2300 v, 3300 v, 4160 v, and 6600 v, 60 hz 3300 v and 6600 v 50 hz variable speed drives
Hide thumbs Also See for YK:
Table of Contents

Advertisement

Section 3 - Installation
• MVVSD not used as service equipment or as a
main section for a separately derived system, and
used on either a grounded or ungrounded system.
1. The MVVSD frame and any ground bus
must be grounded by means or equipment
grounding conductors having size in accor-
dance with NEC Article 250 and run with the
main supply conductors or by bonding to the
raceway enclosing the main supply conduc-
tors in accordance with NEC.
2. Ground leads must be connected to cable
potheads or shields as specified by the cable
manufacturer.

Oil pump wiring

Oil pump field wiring terminals are designated 67, 68,
69, and GND. Standard 14 gauge wire may be used.
The following figure shows the connections for the oil
pump. The 1TB terminals can be found located within
the low voltage compartment at the bottom facing up-
wards.

Table 4 - Control and oil pump wire numbers and termination points for YK chiller

MVVSD connector
location
Wire numbers
Chiller-wire
termination location

Table 5 - Control and oil pump wire numbers and termination points for YD-SYS 1 and YD-SYS 2

MVVSD connector
location
YD-SYS 1
Wire
numbers
YD-SYS 2
Chiller-wire
YD-SYS 1
termination
YD-SYS 2
location
Note: For a YD product, there are two MVVSDs for each YD chiller. The YD has one OptiView panel, which contains two terminal strips. One
strip references the 100 series lines, and the second references the 200 series lines. The 100 series lines connects to one of the MV-
VSDs and the 200 series lines connects to the second MVVSD.
26
24
16
53
24
16
53
OptiView panel - TB6
24
16
53
24
16
53
124
116
153
224
216
253
OptiView panel - TB6
124
116
153
224
216
253
Low voltage section
Remove jumper for
YD/YK-EP applications
24
16
53
L

Figure 11 - Oil pump connections

See Table 4, Table 5, and Table 6 for wire numbers
and termination points for YK, YD, and YKEP units,
respectively.
MVVSD - 1TB
L
2
R24
L
2
n/a
L
2
n/a
MVVSD - 1TB
L
2
R24
L1
N1
R124
L2
N2
R224
OptiView
VSOP cabinet
panel - TB6
L1
N1
2
L2
N2
2
Form 160.00-N6
Issue date: 08/27/2021
1TB
2
R24
67
68
69
67
68
67
68
VSOP cabinet
L1
L2
67
68
167
168
267
268
VSOP cabinet
167
168
267
268
JOHNSON CONTROLS
GND
LD12235b
69
69
L3
69
169
269
169
269