9-3. INSTRUCTION OF TROUBLESHOOTING
Start
Indoor unit operates.
Outdoor unit does not
operate.
Outdoor unit
Outdoor unit
operates only
does not
in Test Run
operate even
operation. *
in Test Run
operation. *
Check room
Refer to "How
temperature
to check
thermistor.
inverter/
Refer to 9-7.
compressor".
"Test point
diagram and
voltage".
Left lamp
Left lamp
Blink on and
2-time blink
off at 0.5-sec-
Cause:
ond intervals
Indoor unit
Cause:
• Trouble of
Indoor/Outdoor
room tem-
unit
perature /
• Miswiring or
indoor coil
trouble of
thermistor
serial signal
Refer to 9-6.
Check room
"How to
temperature
check miswir-
thermistor
ing and serial
and indoor
signal error".
coil thermis-
tor. Refer to
9-7."Test
point diagram
and voltage".
OBH501D
Indoor unit operates.
Indoor unit does not
Outdoor unit does not
receive the signal from
operate normally.
remote controller.
Unit does
Indoor unit oper-
not operate
ates, when the
normally in
emergency oper-
COOL or
ation switch is
HEAT mode
pressed.
operation.
Refer to
Refer to 9-6.
"Check of
"Check of
R.V. coil".
remote controller
and receiver
P.C. board".
Left lamp
Left lamp
3-time blink
4-time blink
Cause:
Cause:
Indoor unit
Indoor unit
• Trouble of
• Trouble of
indoor fan
indoor unit
motor
control sys-
tem
Refer to 9-6.
Replace the
"Check of
indoor elec-
indoor fan
tronic control
motor".
P.C. board.
OPERATION INDICATOR
lamp on the indoor unit is
blinking on and off.
Indoor unit does
not operate,
when the emer-
gency operation
switch is pressed.
1. Check indoor/outdoor
connecting wire.
(Check if the power is
supplied to the indoor
unit.)
2. Refer to 9-6.
"Check of indoor
electronic control P.C.
board and indoor fan
motor".
Left lamp
Left lamp
6-time blink
5-time blink
Cause:
Cause:
Outdoor unit
Outdoor unit
• Trouble of
• Outdoor
power sys-
thermistor in
tem abnor-
outdoor unit
mality
Refer to "How
Refer to
to check
"Check of
inverter/com-
outdoor
pressor".
thermistors".
22
If blinking of OPERATION
INDICATOR lamp cannot be
checked, it can be checked with
failure mode recall function.
* "Test Run operation" means the
operation within 30 minutes after
the emergency operation switch
is pressed.
Refer to outdoor unit service manual.
Left lamp
Left lamp
7-time blink
14-time blink
Cause:
Cause:
Outdoor unit
Outdoor unit
• Trouble of
• Other
outdoor con-
abnormality
trol system
Replace the
Check "Flow
inverter P.C.
chart of the
board or the
detailed out-
outdoor elec-
door unit fail-
tronic control
ure mode
P.C. board.
recall func-
tion."