Mitsubishi Electric MSZ-D30NA Service Manual

Mitsubishi Electric MSZ-D30NA Service Manual

Split-type, heat pump air conditioner
Hide thumbs Also See for MSZ-D30NA:

Advertisement

INDOOR UNIT

SERVICE MANUAL

Wireless type
Models
MSZ-D30NA
MSZ-D36NA
MSY-D30NA
MSY-D36NA
NOTE:
RoHS compliant products have <G> mark on the spec name plate.
Outdoor unit service manual
MUZ-D•NA Series (OBH502)
MUY-D•NA Series (OBH502)
CONTENTS
2. PART NAMES AND FUNCTIONS ····················· 4
3. SPECIFICATION ················································ 5
4. OUTLINES AND DIMENSIONS ························ 7
5. WIRING DIAGRAM ············································ 8
6. REFRIGERANT SYSTEM DIAGRAM ··············· 9
7. SERVICE FUNCTIONS ··································· 10
8. MICROPROCESSOR CONTROL ··················· 12
9. TROUBLESHOOTING ····································· 19
10. DISASSEMBLY INSTRUCTIONS ···················· 31
PARTS CATALOG (OBB501)
No. OBH501
3
·······································

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric MSZ-D30NA

  • Page 1: Table Of Contents

    INDOOR UNIT No. OBH501 SERVICE MANUAL Wireless type Models MSZ-D30NA MSZ-D36NA MSY-D30NA MSY-D36NA Outdoor unit service manual MUZ-D•NA Series (OBH502) MUY-D•NA Series (OBH502) CONTENTS 1. TECHNICAL CHANGES ······································· 2. PART NAMES AND FUNCTIONS ····················· 4 3. SPECIFICATION ················································ 5 4. OUTLINES AND DIMENSIONS ························ 7 5.
  • Page 3: Technical Changes

    TECHNICAL CHANGES MSZ-D30NA MSZ-D36NA MSY-D30NA MSY-D36NA 1. New model...
  • Page 4: Part Names And Functions

    PART NAMES AND FUNCTIONS MSZ-D30NA MSZ-D36NA MSY-D30NA MSY-D36NA Air cleaning filter (Anti-Allergy Enzyme Filter) Front panel Air filter (Catechin air filter) Air inlet Emergency operation switch Air outlet Operation indicator Horizontal vane lamp Remote control Remote controller receiving section MSZ-D30NA...
  • Page 5: Specification

    SPECIFICATION Model MSZ-D30NA MSY-D30NA MSZ-D36NA MSY-D36NA External fi nish White Power supply V, phase, Hz 208 / 230 , 1 , 60 Max. fuse size (time delay)/ Disconnect switch Min. circuit ampacity Fan motor F.L.A 0.76 HEAT Dry 445-639-848 —...
  • Page 6 Model Mode Function (CFM) (ft./sec.) range (ft.) to the position where the air speed is 1 ft./sec., when air is blown out horizon- MSZ-D30NA HEAT 23.6 45.0 tally from the unit properly at the High MSZ-D36NA speed position. MSZ-D30NA 23.6 45.0...
  • Page 7: Outlines And Dimensions

    OUTLINES AND DIMENSIONS MSZ-D30NA Unit : inch MSZ-D36NA MSY-D30NA MSY-D36NA Indoor unit 2-11/16 4-11/16 45-1/2 2-3/16 20-7/8 17-11/16 5-3/8 11-5/8 Wall hole ø3 Air in 46-1/16 Installation plate Piping Drain hose 2-15/16 33-11/16 9-1/2 2-5/8 5-7/8 Air out Piping 2-5/16 Insulation ø3/8 19-11/16...
  • Page 8: Wiring Diagram

    WIRING DIAGRAM MSZ-D30NA MSZ-D36NA MSY-D30NA MSY-D36NA...
  • Page 9: Refrigerant System Diagram

    REFRIGERANT SYSTEM DIAGRAM MSZ-D30NA Unit:inch MSZ-D36NA MSY-D30NA MSY-D36NA Refrigerant pipe ø5/8 (with heat insulator) Indoor coil Indoor thermistor heat exchanger RT12(main) Flared connection Indoor coil Distributor Joint thermistor Joint connection RT13(sub) Room temperature thermistor RT11 Flared connection Strainer Refrigerant flow in cooling Refrigerant pipe ø3/8...
  • Page 10: Service Functions

    SERVICE FUNCTIONS MSZ-D30NA MSZ-D36NA MSY-D30NA MSY-D36NA 7-1. TIMER SHORT MODE For service, set time can be shortened by short circuit of JPG and JPS the indoor electronic control P.C. board. The time will be shortened as follows. (Refer to 9-7.)
  • Page 11 7-3. AUTO RESTART FUNCTION When the indoor unit is controlled with the remote controller, the operation mode, the set temperature, and the fan speed are memorized by the indoor electronic control P.C. board. The “AUTO RESTART FUNCTION” sets to work the moment power has restored after power failure.
  • Page 12: Microprocessor Control

    MICROPROCESSOR CONTROL MSZ-D30NA MSZ-D36NA MSY-D30NA MSY-D36NA WIRELESS REMOTE CONTROLLER These pictures show MSZ type. Signal transmitting section Operation display section OPERATE/STOP (ON/OFF) button VANE CONTROL button FAN SPEED (Horizontal vane button) CONTROL button Temperature buttons OFF TIMER button OPERATION SELECT button...
  • Page 13 8-1. COOL ( ) OPERATION (1) Press OPERATE/STOP (ON/OFF) button. OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone. (2) Select COOL mode with OPERATION SELECT button. (3) Press TEMPERATURE buttons (TOO WARM or TOO COOL button) to select the desired temperature. The setting range is 61 ~ 88 °F (16 ~ 31 °C).
  • Page 14 (4) The initial set temperature is decided by the initial room temperature. Model Initial room temperature Initial set temperature 79 °F (26 °C) or more 75°F (24 °C) COOL mode of "I FEEL CONTROL" 77 °F (25 °C) to 79 °F (26 °C) Initial room temperature minus 4 °F (2 °C) DRY mode of "I FEEL more than 55 °F (13 °C), Initial room temperature minus 4 °F (2 °C)
  • Page 15 8-7. AUTO VANE OPERATION 1. Horizontal vane (1) Vane motor drive These models are equipped with a stepping motor for the horizontal vane. The rotating direction, speed, and angle of the motor are controlled by pulse signals (approx. 12 V) transmitted from indoor microprocessor. (2) The horizontal vane angle and mode change as follows by pressing VANE CONTROL button.
  • Page 16 2. Vertical vane (1) Vane motor drive These models are equipped with a stepping motor for the vertical vane. The rotating direction, speed, and angle of the motor are controlled by pulse signals (approx. 12 V) transmitted from microprocessor. (2) The vertical vane angle and mode change as follows by pressing WIDE VANE button. SWING (3) Positioning The vane is once pressed to the vane stopper to confirm the standard position and then set to the desired angle.
  • Page 17 8-8. TIMER OPERATION 1. How to set the time (1) Check that the current time is set correctly. NOTE : Timer operation will not work without setting the current time. Initially “0:00” blinks at the current time display of TIME MONITOR, so set the current time correctly with CLOCK SET button. How to set the current time (a) Press the CLOCK set button.
  • Page 18 8-9. EMERGENCY/TEST OPERATION In case of test run operation or emergency operation, use EMERGENCY OPERATION switch on the front of the indoor unit. Emergency operation is available when the remote controller is missing, has failed or the batteries of the remote controller run down.
  • Page 19: Troubleshooting

    TROUBLESHOOTING MSZ-D30NA MSZ-D36NA MSY-D30NA MSY-D36NA 9-1. CAUTIONS ON TROUBLESHOOTING 1. Before troubleshooting, check the following 1) Check the power supply voltage. 2) Check the indoor/outdoor connecting wire for miswiring. 2. Take care of the following during servicing 1) Before servicing the air conditioner, be sure to turn off the unit first with the remote controller, and then after confirm- ing the horizontal vane is closed, turn off the breaker and / or disconnect the power plug.
  • Page 20: Failure Mode Recall Function

    9-2. FAILURE MODE RECALL FUNCTION Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (9-4.) disappears, the memorized failure details can be recalled. This mode is very useful when the unit needs to be repaired for the abnormality which doesn't recur.
  • Page 21 2. Indoor unit failure mode table Left lamp of OP- Abnormal point ERATION INDICA- Condition Correspondence (Failure mode) TOR lamp Not lighted Normal — — The room temperature thermistor short or open 1-time fl ash every Room temperature Refer to the characteristics of the room temperature circuit is detected every 8 seconds during op- 0.5-second thermistor...
  • Page 22 9-3. INSTRUCTION OF TROUBLESHOOTING Start Indoor unit operates. Indoor unit Indoor unit oper- OPERATION INDICATOR Outdoor unit doesn't ates. doesn't receive lamp on the indoor unit is operate normally. the signal from Outdoor unit fl ashing on and off. remote controller. doesn't operate.
  • Page 23: Troubleshooting Check Table

    9-4. TROUBLESHOOTING CHECK TABLE Before taking measures, make sure that the symptom reappears for accurate troubleshooting. When the indoor unit has started operation and the following detection method has detected an abnormality (the first detection after the power ON), the indoor electronic control P.C. board turns OFF the indoor fan motor with OPERATION INDICATOR lamp flashing.
  • Page 24 9-5. TROUBLE CRITERION OF MAIN PARTS MSZ-D30NA MSZ-D36NA MSY-D30NA MSY-D36NA Part name Check method and criterion Figure Room temperature Measure the resistance with a tester. thermistor(RT11) Refer to 9-7. "Test point diagram and voltage", "Indoor electronic control P.C. Indoor coil thermistor board", the chart of thermistor.
  • Page 25: Troubleshooting Flow

    9-6. TROUBLESHOOTING FLOW OPERATION INDICATOR lamp flashes 3-time. Indoor fan does not operate. A Check of indoor fan motor The indoor fan motor error has occurred, and the indoor fan doesn't operate. Turn OFF the power supply. Pay careful attention to the high voltage on the fan motor connector CN211. Turn ON the power supply, wait 5 seconds or more, and then press EMERGENCY OPERATION switch.
  • Page 26 Indoor unit operates by pressing EMERGENCY OPERATION switch, but does not operate with the remote controller. B Check of remote controller and receiver P.C. board Check if the remote controller is exclusive for this air conditioner. Switch ON the remote controller. Is LCD display on the remote controller Replace the batteries.
  • Page 27 The unit does not operate with the remote controller. Also, OPERATION INDICATOR lamp does not light up by pressing EMERGENCY OPERATION switch. C Check of indoor electronic control P.C. board and indoor fan motor Turn OFF the power supply. Remove indoor fan motor connector CN211 Measure the resistance between Short/open circuit: CN211...
  • Page 28 • Unit cannot operate neither by the remote controller nor by EMERGENCY OPERATION switch. Indoor unit does not operate. • OPERATION INDICATOR lamp flashes ON and OFF every 0.5-second. Outdoor unit does not operate. D How to check miswiring and serial signal error Turn OFF the power supply.
  • Page 29 E Electromagnetic noise enters into TV sets or radios Is the unit grounded? Ground the unit. Is the distance between the antennas Extend the distance between the antennas and and the indoor unit within 9.91 ft., or is the indoor unit, and/or the antennas and the the distance between the antennas and outdoor unit.
  • Page 30 9-7. TEST POINT DIAGRAM AND VOLTAGE MSZ-D30NA MSZ-D36NA MSY-D30NA MSY-D36NA Indoor electronic control P.C. board Power supply input Cement resistor (R111) Varistor (NR11) 208 / 230 VAC Fuse (F11) 250 V 3.15 A Indoor fan motor Release of Auto restart function...
  • Page 31: Disassembly Instructions

    Pull the terminal while pull out the terminal pushing the locking slowly. Locking lever lever. Connector 10-1. MSZ-D30NA MSZ-D36NA MSY-D30NA MSY-D36NA OPERATING PROCEDURE PHOTOS 1. Removing the panel Photo 1 Front panel (1) Press and unlock the knobs on both sides of the front panel and lift the front panel until it is level, and then pull the hinges forward to remove the front panel.
  • Page 32 OPERATING PROCEDURE PHOTOS Photo 3 3. Removing the nozzle assembly (1) Remove the panel and the corner box. (Refer to 1.) (2) Remove the electrical cover. (Refer to 2.) (3) Remove the electrical side cover, disconnect the vane Screw of electrical motor connector.
  • Page 33 OPERATING PROCEDURE PHOTOS Photo 7 6. Removing the line flow fan and the indoor fan motor (1) Remove the panel and the corner box. (Refer to 1.) (2) Remove the electrical box. (Refer to 2.) Screw of the motor band (3) Remove the nozzle assembly.
  • Page 36 HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN Copyright 2008 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD New publication, effective Feb. 2008 Distributed in Feb. 2008. No. OBH501 7 Specifications subject to change without notice. Made in Japan...