Panel Cutout - Omron E5GN-QTD Manual

Digital temperature controller
Table of Contents

Advertisement

E5GN
Dimensions
Unit: mm (inch)

E5GN
48
(1.89)
24
35
(1.38)
44.8
(1.76)

Panel Cutout

Mounted Separately
60 min.
60 min.
+0.6
45
0
3
36.8
(1.45)
* When carrying out maintenance on the E5GN, only the terminal plate can be drawn
22
out with the terminal leads still attached.
(0.87)
Group Mounted
Mounting separately does not allow waterproofing.
Insert the Controller through the hole in the panel from the front and push the adapter on
from the rear. Push the adapter up to the back of the panel, ensuring that the controller
is pushed all the way in, and remove any gap between the Controller, the panel, and the
+0.3
22
adapter. Finally, use the two screws on the adapter to secure the unit in place.
0
To mount the E5GN so that it is waterproof, insert the waterproof seal onto the E5GN.
When two or more E5GN Controllers are mounted, make sure that the surrounding
temperature does not exceed the allowable operating temperature given in the
specifications.
100
(3.94)

+1.0
(48
number of units -2.5)
0
E5GN
22
(0.87)
+0.3
22
0

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5gnE5gn-q2tE5gn-r2tE5gn-q1tE5gn-rtE5gn-c1l

Table of Contents