Installation Of Outdoor Unit - LG UU85W Installation Manual

Table of Contents

Advertisement

INSTALLATION OF OUTDOOR UNIT

You need to select adequate installation location considering the following conditions, and make
sure to acquire the consent of the user.
Installation Places
- If an awning is built over the unit to prevent
direct sunlight or rain exposure, make sure
that heat radiation from the condenser is not
restricted.
- Ensure that the spaces indicated by arrows
around front, back and side of the unit.
- Do not place animals and plants in the path
of the warm air.
- Take the air conditioner weight into account
and select a place where noise and vibration
are minimum.
- Select a place so that the warm air and noise
from the air conditioner do not disturb neigh-
bors.
- Place that can sufficiently endure the weight and vibration of the outdoor unit and where even
installation is possible.
- Place that has no direct influence of snow or rain
- Place with no danger of snowfall or icicle drop
- Place without weak floor or base such as decrepit part of the building or with a lot of snow ac-
cumulation
- Install at a place with fluent water draining to prevent damage from localized heavy rain and
avoid frequent flooded area.
Piping length and the elevation
• Single Operation
Pipe Size mm(inch)
Model
Gas
UU85W
Ø22.2(7/8) Ø12.7(1/2)
If installed tube is shorter than 15 m, addi-
tional charging is not necessary.
Additional Refrigerant
= (A-15) x Additional refrigerant (g)
Length A(m)
Liquid
Standard
15
INSTALLATION OF OUTDOOR UNIT
More than
300mm
F e
n c e
o b
o r
s t a
c l e
s
Elevation B(m)
Max.
Standard
75
5
Indoor unit
A
B
Outdoor unit
More than
More than
More than
300mm
300mm
300mm
More than 600mm
More than 700mm
Unit : mm
Additional
refrigerant
Max.
(g/m)
30
70
Outdoor unit
A
Indoor unit
B
7

Advertisement

Table of Contents
loading

Table of Contents