Installation; The Location Of The Anchor Bolts - LG UU85W Installation Manual

Table of Contents

Advertisement

INSTALLATION

12
INSTALLATION
- Install at places where it can endure the weight and vibration/noise of the outdoor unit.
- The outdoor unit supports at the bottom shall have width of at least 100mm under the Unit's
legs before being fixed.
- The outdoor unit supports should have minimum height of 200mm.
- Anchor bolts must be inserted at least 75mm.
For outdoor units should not
be supported only by the
corner supports.

The location of the Anchor bolts

Center of the Unit
1,090
700
Center of the Unit
[Unit : mm]