Precautions On Refrigerant Piping; Refrigerant Pipe Size And Allowable Pipe Length; Connecting The Refrigerant Piping - Daikin R200F7W1 Installation Manual

Hide thumbs Also See for R200F7W1:
Table of Contents

Advertisement

4. The space around the unit is adequate for servicing and the
minimum space for air inlet and air outlet is available.
(Refer to figure 1 and choose one of both possibilities.)
5. There is no danger of fire due to leakage of flammable gas.
6. Ensure that water cannot cause any damage to the location in
case it drips out the unit (e.g. in case of a blocked drain pipe).
7. Select the location of the unit in such a way that neither the
discharged air nor the sound generated by the unit disturb
anyone.
P
RECAUTIONS
Do not install or operate the unit in sites mentioned below.
• Where mineral oil like cutting oil is present;
• Where the air contains high levels of salt;
• Where sulphurous gas exists such as at areas with hot springs;
• Where voltage fluctuates a lot;
• In vehicles or vessels;
• Where high concentrations of oil vapour or spray are present;
• Where machines generating excessive electromagnetic waves
are installed;
• Where acidic or alkaline vapour is present.
Caution
In heavy snowfall areas, select an installation site where snow
will not affect operation of the unit.
R
EFRIGERANT PIPING
All field piping must be installed by a licensed refrigeration
technician and must comply with relevant local and national
regulations.
R
EFRIGERANT PIPE SIZE AND ALLOWABLE PIPE LENGTH
Refrigerant pipe size
1. Pair system (Refer to figure 5A)
Gas
R(Y)200
Ø25.4
R(Y)250
Ø28.6
2. Simultaneous operation system
• Twin and Triple operation system (Refer to figure 5B and 5C)
Caution
The pipes between the outdoor unit and the branch
have the same size as the outdoor connections.
The pipes between the branch
have the same size as the indoor connections.
• Double twin operation system (Refer to figure 5D)
L1
Gas
Liquid
R(Y)200
Ø25.4
Ø12.7
R(Y)250
Ø28.6
Ø15.9
Refrigerant pipe size
Liquid
Ø12.7
Ø15.9
should
and the indoor units should
Refrigerant pipe size
L2 - L3
L4 - L5 - L6 - L7
Gas
Liquid
Gas
Liquid
Ø19.1
Ø9.5
Ø12.7
Ø6.4
Ø19.1
Ø9.5
Ø15.9
Ø9.5
Allowable pipe length
L1
max. allowable piping length
L1 + L2, L1 + L3, L1 + L4
L1 + L2 + L3
L2, L3, L4
max. branch pipe length
L2 + L4
L1 - L2, L2 - L4, L3 - L4
max. difference between
branch lengths
(L2 + L4) - (L3 + L7)
max. difference between each
L2 - L3
1st branch
max. difference between each
L4 - L5, L6 - L7
2nd branch
H1, H2, H3
max. height difference between
indoors
H1, H2, H3, H4, H5
max. height difference between
H
indoor and outdoor
P
RECAUTIONS ON REFRIGERANT PIPING
When the outdoor unit is installed below the indoor unit, the
following can occur:
• When the unit stops, oil will return to the discharge side of the
compressor. When starting the unit, this can cause liquid (oil)
hammer.
• The oil circulation will decrease.
To solve these phenomena, provide oil traps in the gas pipe every
15 m if the level difference (H) is more than 15 m.
1
1. Outdoor unit
2. Indoor unit
3. Gas pipe
4. Liquid pipe
5. Oil trap
Note
If the outdoor unit is installed above the indoor unit, oil traps
are not necessary.
C
ONNECTING THE REFRIGERANT PIPING
1. Installation of refrigerant piping is possible as front connection,
side connection and bottom connection.
1. Flange
2. Flare nut
3. Gas side attached pipe
4. Liquid side attached pipe
5. Brazing
6. Knock out hole (use a hammer)
pair
twin/triple
double twin
50 m
-
-
-
50 m
-
-
-
50 m
-
20 m
-
-
-
20 m
-
10 m
-
-
-
10 m
-
-
10 m
-
-
10 m
-
0,5 m
-
-
-
0,5 m
30 m
30 m
30 m
2
5
3
4
2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

R250f7w1Ry200f7w1Ry250f7w1

Table of Contents