Outdoor Fan; Electrical Controls And Wiring - Carrier bryant 577C-C Installation Instructions Manual

Table of Contents

Advertisement

COMPRESSOR
ACCESS PANEL
Fig. 20 - - Unit Access Panels
Fig. 21 - - Removal of Motor and Blower Wheel
CONTROL
ACCESS
PANEL
BLOWER
ACCESS
PANEL
A170032
BLOWER
HOUSING
2 SETSCREWS
(HIDDEN)
C99085
53
Fig. 22 - - Burner Rack Removed

Outdoor Fan

CAUTION
!
UNIT OPERATION HAZARD
Failure to follow this caution may result in damage to unit
components.
Keep the condenser fan free from all obstructions to ensure
proper cooling operation. Never place articles on top of the
unit.
1. Remove 6 screws holding outdoor grille and motor to top
cover.
2. Turn motor/grille assembly upside down on top cover to
expose fan blade.
3. Inspect the fan blades for cracks or bends.
4. If fan needs to be removed, loosen setscrew and slide fan off
motor shaft.
5. When replacing fan blade, position blade as shown in Fig.
23.
6. Ensure that setscrew engages the flat area on the motor shaft
when tightening.
7. Replace grille.

Electrical Controls and Wiring

Inspect and check the electrical controls and wiring annually. Be
sure to turn off the electrical power to the unit.
Remove access panels (see Fig. 20) to locate all the electrical
controls and wiring. Check all electrical connections for tightness.
Tighten all screw connections. If any smoky or burned connections
are noticed, disassemble the connection, clean all the parts, re- -strip
the wire end and reassemble the connection properly and securely.
After inspecting the electrical controls and wiring, replace all the
panels. Start the unit, and observe at least one complete cooling
cycle to ensure proper operation. If discrepancies are observed in
operating cycle, or if a suspected malfunction has occurred, check
each
electrical
component
instrumentation. Refer to the unit wiring label when making these
checks.
A07680
with
the
proper
electrical

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bryant 577c-e