Carrier bryant 577C-C Installation Instructions Manual page 7

Table of Contents

Advertisement

CAUTION - NOTICE TO RIGGERS
PRUDENCE - AVIS AUX MANIPULATEUR
Use top skid as spreader bar. / Utiliser la palette du haut comme barre de répartition
SEE DETAIL A
VOIR DÉTAIL A
SMALL CABINET
24
Unit
lb
kg
Rigging Weight
329
149
NOTE: See dimensional drawing for corner weights.
UNIT SIZE
NOMINAL CAPACITY (ton)
SHIPPING WEIGHT lb.
SHIPPING WEIGHT (kg)
COMPRESSOR / QUANTITY
REFRIGERANT (R --- 410A)
Quantity lb.
Quantity (kg)
REFRIGERANT METERING DEVICE
ORIFICE ID in. / mm
OUTDOOR COIL
Rows...Fins/in.
Face Area (sq ft)
OUTDOOR FAN
Nominal CFM
Diameter in.
Diameter (mm)
Motor Hp (Rpm)
INDOOR COIL
Rows...Fins/in.
Face Area (sq ft)
INDOOR BLOWER
Nominal Cooling Airflow (Cfm)
Size in.
Size (mm.)
Motor HP (RPM)
FURNACE SECTION*
Burner Orifice No. (Qty...Drill Size)
1 Phase Natural Gas (Factory Installed)
1 Phase Propane Gas
3 Phase Natural Gas (Factory Installed)
3 Phase Propane Gas
HIGH --- PRESSURE SWITCH
(psig) Cut--- out Reset (Auto)
LOSS- -OF- -CHARGE / LOW- -PRESSURE
SWITCH (Liquid Line) (psig) cut- -out
Reset (auto)
RETURN--- AIR FILTERS†}
Throwaway Size in.
(mm)
*Based on altitude of 0 to 2000 ft (0 ---610 m).
{ Required filter sizes shown are based on the larger of the AHRI (Air Conditioning Heating and Refrigeration Institute) rated cooling airflow or the heating air-
flow velocity of 300 to 350 ft/minute for throwaway type. Air filter pressure drop for non ---standard filters must not exceed 0.08 IN. W.C.
} If using accessory filter rack refer to the filter rack installation instructions for correct filter sizes and quantity.
ACCESS PANELS MUST BE IN PLACE WHEN RIGGING.
PANNEAUX D'ACCES DOIT ÊTRE EN PLACE POUR MANIPULATION.
MINIMUM HEIGHT: 36" (914.4 mm)
HAUTEUR MINIMUM
UNIT HEIGHT
HAUTEUR D'UNITÉ
30
36
lb
kg
lb
kg
361
164
390
177
Fig. 6 - - Unit Suggested Rigging
Table 1 – Physical Data
24040
24060
2
2
329
329
149
149
Rotary / 1
5.3
5.3
2.4
2.4
.059 / 1.5
.059 / 1.5
1..21
1...21
11.9
11.9
2500
2500
24
24
609.6
609.6
1/10 (810)
1/10 (810)
3...17
3...17
3.7
3.7
800
800
800
800
10x10
10x10
254x254
254x254
1/2 (1050)
1/2 (1050)
2...44
3...44
2...55
3...55
DUCTS
SEAL STRIP MUST BE IN
PLACE BEFORE PLACING
UNIT ON ROOF CURB
DETAIL A
VOIR DÉTAIL A
Unit
lb
Rigging Weight
455
30040
30060
2 ---1/2
2 ---1/2
361
361
164
164
6.4
6.4
2.9
2.9
Orifice
.061 / 1.55
.061 / 1.55
1...21
1...21
13.6
13.6
2700
2700
24
24
609.6
609.6
1/10 (810)
1/10 (810)
3...17
3...17
3.7
3.7
1000
1000
1000
1000
10x10
10x10
254x254
254x254
1/2 (1050)
1/2 (1050)
2...44
3...44
2...55
3...55
2...44
2...38
2...55
2...53
650 +/-- 15
420 +/-- 25
20 +/-- 5
45 +/-- 10
2 each 20x12x1
508x305x25
7
BANDE SCELLANT DOIT ÊTRE
EN PLACE AVANT DE PLACER
L'UNITÉ SUR LA BASE DE TOIT
50CY502286 2.0
LARGE CABINET
42
48
kg
lb
kg
lb
206
480
218
497
36060
36090
42060
3
3
3 ---1/2
390
390
455
177
177
206
Scroll / 1
8.2
8.2
6.2
3.7
3.7
2.8
TXV
N/A
.073 / 1.85
1...21
1...21
1...21
18.8
18.8
13.6
3200
3200
3600
24
24
26
609.6
609.6
660.4
1/5 (810)
1/5 (810)
1/5 (810
3...17
3...17
3...17
3.7
3.7
4.7
1150
1150
1150
1150
1350
1350
11x10
11x10
11x10
279.4x254
279.4x254
279.4x254
3/4 (1000)
3/4 (1000)
1/2 (1050)
3...44
3...38
3...44
3...55
3...53
3...55
2...38
3...38
2...38
2...53
3...53
2...53
1 each 24x14x1
610x356x25
610x406x25
A09051
60
kg
225
42090
3 ---1/2
455
206
6.2
2.8
Orifice
.073 /1.85
1...21
13.6
3600
26
660.4
1/5 (810)
3...17
4.7
1350
1350
11x10
279.4x254
1/2 (1050)
3...38
3...53
3...38
3...53
24x15x1