NOTE
A shielded cable must be used and connected to local ground at both the subscriber unit and lightning
protector.
NOTE
The lightning protector must meet the necessary requirements of IEC/UL/CSA 60950-1. The clamping
voltage must also be less than 60 V and the protector must not activate when the voltage is less than
56 V. For more information about these requirements, contact Siemens Customer Support.
IMPORTANT!
Install the lightning protector and the RUGGEDCOM RP100/RP110 as close as possible.
Figure 6: Typical Outdoor Installation
1. RUGGEDCOM WIN5251    2. Shielded Cable    3. Ground Connection    4. Lightning Protector    5. RUGGEDCOM RP100/RP110    6. Drain
Wire (Shielded)
For more information about the RUGGEDCOM RP100 or RP110, refer to the RUGGEDCOM RP100 Installation Guide
or the RUGGEDCOM RP110 Installation Guide.
Section 2.6.3

Assembling the PoE Connector

A custom PoE cable with a special RJ45 connector is required to connect a PoE injector to the DC/ETH port. The
following materials and tools are required:
• The RJ45 connector kit (included). Contains an RJ45 connector and loading bar.
• CAT-5e cable of suitable length for your application. For information on cable specifications, refer to
Section 4.5, "IDU to ODU Cable
• Standard cable splicing tools, including a standard crimp tool.
To assemble the PoE connector, do the following:
1.
Slide the connector components on to the wire.
Assembling the PoE Connector
1
6
3
Specifications".
2
4
3
3