Power supply and wire specification
f For heat pump products, power supply for heating must be separately installed.
X
Model name
Power
Power input
Cooling
Running current
Power input
Heating
Running current
Starting current
Power cable
Below 20m
Over 20m
Circuit breaker
Thickness of the earth wire
Fuse capacity for control circuit
PAC_아프리카 중동향AP80S0A_IBIM_34514A-02_EN.indd 41
W
A
W
A
A
Type
mm
2
mm
2
A
mm
2
A
AP80S0A
3 phase 4 wires 380-415V, 50Hz
6,600
12.0
-
-
Equivaletnt to H07RN-F or higher
4.0(Not included)
6.0(Not included)
30
4
20
AP0AS0A
9,800
16.5
-
-
4.0(Not included)
6.0(Not included)
40
4
20
41
2015-04-23 오후 2:18:59