LG PQCPA11A0E Installation & Owner's Manual page 72

Advanced control platform air conditioner
Table of Contents

Advertisement

2. Installing ACP
Dip switch
Physical address
Model name
Maximum consumed power
9.
For the remaining three groups, set the number of the indoor units and the item by the procedure
same to Step 7 and 8.
10.
When all items are set, press [Save] button to save. Press [Save] button to display the window to
confirm to save the setting information. Press [OK] button to save the setting information.
Press [Save] button to the setting.
When the confirmation window is
2-58
ACP
Enter the physical address of the indoor unit. The physical address
consists of three numbers.
The first number and the second number are the G/W number and the
outdoor unit number respectively, which can be set within the
information entered from the existing [G/W information] and [outdoor
unit information].
The third number is the indoor unit number, which can not be set
overlapped within the same indoor unit number and should be set
within the range of 0~15.
If the user directly enters the physical address, it can be easily entered
incorrectly. So, [Default value] button should be used to enter.
Enter the model name of the indoor unit.
Enter the maximum consumed power for the indoor unit to use. The maximum
consumed power depends on the model.
displayed, press [OK] button.
Description

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pqcpb11a0e

Table of Contents