Commissioning the system
Parameters for ice store system
Parameter
"System definition"
Ó
"Select primary source 7030"
"External extension 7010"
"Solar"
Ó
"Type solar control unit 7A00"
Possibly set additional parameters.
"System definition"
Ó
"Start hysteresis solar air absorber 7031"
"Min. runtime to suppress summer mode 7035"
"Last calendar week for summer mode 7036"

Checking the system function

Check the function of all system components, e.g.
circulation pumps, 3-way diverter valves.
Scan temperatures at the heat pump control unit.
Possibly check heat meter readings.
Resetting the high limit safety cut-out
!
Please note
If the heat pump is exposed to temperatures
below
15 °C, e.g. during storage or transport,
the high limit safety cut-out of the instantaneous
heating water heater may respond.
Heat up high limit safety cut-out to above 20 °C
and press the high limit safety cut-out reset but-
ton (see Fig. 40).

Instructing the system user

The system installer should hand the operating instruc-
tions to the system user and instruct the user in oper-
ating the system.
This includes all components installed as accessories,
e.g. remote control units. In addition, the system instal-
ler must make the user aware of the required mainte-
nance work.
Commissioning, inspection, maintenance
(cont.)
Setting
"1"
"2"
"2"
"0" to "500" (
"0" to "1440" min
Calendar week "1" to "53"
A
Fig. 40
Reset button
A
0 to 50 K)
51