Checking The System Function; Temperatures, Heat Meter If Applicable) - Viessmann VITOCAL 222-S Installation And Service Instructions Manual

Compact heat pumps, split version for heating and cooling operation
Table of Contents

Advertisement

Further details regarding the individual steps
Energy meter
Electricity meter parameters
"Photovoltaics" Ó
"Enable own energy consumption PV 7E00"
Extended menu:
"PV ctrl strategy"
or
"Photovoltaics" Ó
■ "Enable own energy consumptn for set DHW
temperature 2 7E10"
■ "Enable own energy consumption for DHW
heating 7E11"
■ "Enable own energy consumptn for heating
water buffer cyl. 7E12"
■ "Enable own energy consumption for heat-
ing 7E13"
Extended menu:
"PV ctrl strategy"
or
"Photovoltaics" Ó
■ "Raise set DHW cylinder temperature PV
7E21"
■ "Raise set heating water buffer cylinder
temp PV 7E22"
■ "Raise set room temperature PV 7E23"
Checking the system function (e.g. actuators, temperatures, heat
meter if applicable)
!
Please note
If the heat pump is exposed to
temperatures below –15 °C, e.g.
during storage or transport, the
high limit safety cut-out of the
instantaneous heating water
heater may respond.
Heat up the high limit safety cut-
out to above 20 °C and press
reset button A on the high limit
safety cut-out.
Commissioning, inspection, maintenance
(cont.)
Setting
"1"
Enable the required functions/
system components for own en-
ergy consumption.
"1"
"1"
"1"
"1"
Specify the temperature differen-
tial to the selected set value for
the chosen energy consumer.
"0" to "200"
(≙ 0 to 20 °C)
"0" to "100"
(≙ 0 to 10 °C)
"0" to "50"
(≙ 0 to 5 °C)
85