18.1.2 Refrigerant piping insulation
18.1.3 To select the piping size
REYQ8~20+REMQ5U7Y1B
VRV IV+ heat recovery
4P561154-1A – 2020.10
NOTICE
The piping and other pressure-containing parts shall be suitable for refrigerant. Use
phosphoric acid deoxidised seamless copper for refrigerant.
▪
Only use phosphoric acid deoxidised seamless copper.
▪
Foreign materials inside pipes (including oils for fabrication) must be
≤30 mg/10 m.
▪
Temper grade: use piping with temper grade in function of the pipe diameter as
listed in table below.
Pipe Ø
≤15.9 mm
≥19.1 mm
▪
All piping lengths and distances have been taken into consideration (see
4
the piping
length" [
75]).
▪
Use polyethylene foam as insulation material:
-
with a heat transfer rate between 0.041 and 0.052 W/mK (0.035 and
0.045 kcal/mh°C)
-
with a heat resistance of at least 120°C
▪
Insulation thickness
Ambient temperature
≤30°C
>30°C
Determine the proper size using the following tables and reference figure (only for
indication).
a
A
D
E
3
4
b
E
1
2
1,2 VRV DX indoor unit
3 Branch selector unit (BS*)
4 Cooling-only VRV indoor unit
A~E Piping
a,b Indoor branch kit
x,y Outdoor multi connection kit
Temper grade of piping material
Humidity
75% to 80% RH
≥80% RH
C
C
x
y
B
18
Piping installation
|
O (annealed)
1/2H (half hard)
Minimum thickness
15 mm
20 mm
C