Standard Accessories; Electrical Requirement; Selecting The Mounting Position; Installation Diagram Of Indoor And Outdoor Units - Friedrich MR09C1F Installation Manual

Split type room air conditioner
Hide thumbs Also See for MR09C1F:
Table of Contents

Advertisement

GENERAL
This INSTALLATION MANUAL briefly outlines where
and how to install the air conditioning system. Please
read over the entire set of instructions for the indoor
and outdoor units and make sure all accessory parts
listed are with the system before beginning.
1. TYPE OF COPPER PIPE AND INSULATION MATERIAL
Copper tubing for connectin the outdoor unit to the indoor
unit and insulation material is available for purchase locally.
When you purchase them, please specify the following.
A. Deoxidized annealed copper pipe for refrigerant piping as:
Table 3
Small pipe
Large pipe
Outer diameter
Thickness
Outer diameter
Thickness
1/4"(6.35 mm)
1/32"(0.8 mm)
3/8"(9.52 mm)
1/32"(0.8 mm)
Cut each pipe to the appropriate length +12" (30 cm)
to16" (40 cm) to dampen vibration between units.
B. Foamed polyethylene insulation for copper pipes as
required to precise length of piping. Wall thickness
of the insulation should not be less than 5/16" (8 mm).
C. Use insulated copper wire for field wiring.
CAUTION
Check local electrical codes and regulations
before obtaining wire. Also, check any specified
instructions or limitations.
2. ADDITIONAL MATERIALS REQUIRED FOR INSTALLATION
A. Refrigeration (armored) tape
B. Insulated staples or clamps for connecting wire
(See your local electrical codes.)
C. Putty
D. Refrigeration lubricant
E. Clamps or saddles to secure refrigerant piping
3. OPERATING RANGE
Table 4
Heating Mode
Cooling/Dry Mode
Outdoor temperature
About 32 to 115 °F
About 17 to 75 °F
Indoor temperature
About 64 to 90 °F
88 °F or less
Outdoor
About 80% or less
temperature
68°F or obove
Indoor
Outdoor
About 50% or less
Humidity
temperature
below 68°F
ADDITIONAL CHARGE
Refrigerant suitable for a piping length of 25 ft (7.5 m) is charged in
the outdoor unit at the factory.
When the piping is longer than 25 ft (7.5 m), additional charging is necessary.
For the additional amount, see the table below.
Table 5
Pipe length
25 ft (7.5 m)
33 ft (10 m)
49 ft (15 m)
Additional
None
1.8 oz (50 g)
5.3 oz (150 g)
refrigerant
Between 25 ft (7.5 m) and 49 ft (15 m), when using a connection pipe
other than that in the table, charge additional refrigerant with 0.7 OZ/
3.3 ft (20g/1 m) as the criteria.
CAUTION
(1) When adding refrigerant, add the refrigerant from
the charging port at the completion of work.
(2) The maximum length of the piping is 15 m. If the
units are further apart than this, correct opera-
tion can not be guaranteed.

STANDARD ACCESSORIES

The following installation accessories are supplied. Use them as re-
quired.
INDOOR UNIT ACCESSORIES
Name and Shape
Q'ty
Use
Wall hook bracket
For indoor unit installation
1
Remote
Use for air conditioner
control unit
operation
1
Battery (penlight)
For remote control unit
2
Cloth tape
For indoor unit installation
1
Remote control
Use as remote control unit
unit holder
holder
1
Tapping screw (big)
For wall hook bracket
(ø4 × 20)
installation
8
Tapping screw (small)
For remote control unit
(ø3 × 12)
holder installation
2
The following items are necessary to install this air conditioner. (The
items are not included with the air conditioner and must be purchased
separately.)
Name
Connection pipe assembly
Connection cord (3-conductor)
Wall pipe
Decorative tape
Vinyl tape
Wall cap
Saddle
Drain hose
Tapping screws
Sealant

ELECTRICAL REQUIREMENT

Always make the air conditioner power supply a special branch cir-
cuit and provide a special switch and receptacle. Do not extend the
power cord.
CAUTION
9000 BTU/h 12000 BTU/h
MINIMUM CIRCUIT AMPACITY
12 A
MAXIMUM OVERCURRENT PROTECTION
15 A
(TIME DELAY FUSE OR HACR TYPE CIRCUIT BREAKER)
SELECTING THE MOUNTING
POSITION
Decide the mounting position with the customer as follows:
1. INDOOR UNIT
(1) Install the indoor unit level on a strong wall which is not subject
to vibration.
(2) The inlet and outlet ports should not be obstructed : the air should
be able to blow all over the room.
(3) Install the unit near an electric outlet or special branch circuit.
(4) Do not install the unit where it will be exposed to direct sunlight.
(5) Install the unit where connection to the outdoor unit is easy.
(6) Install the unit where the drain pipe can be easily installed.
(7) Take servicing, etc. into consideration and leave the spaces shown
in (Fig. 2). Also install the unit where the filter can be removed.
2. OUTDOOR UNIT
(1) If possible, do not install the unit where it will be exposed to di-
rect sunlight. (If necessary, install a blind that does not interfere
with the air flow.)
(2) Do not install the unit where a strong wind blows or where it is
very dusty.
(3) Do not install the unit where people pass.
(4) Take you neighbors into consideration so that they are not dis-
turbed by air blowing into their windows or by noise.
(5) Provide the space shown in Fig. 2 so that the air flow is not blocked.
Also for efficient operation, leave open three of the four direc-
tions front, rear, and both sides.
WARNING
Install at a place that can withstand the weight of the
indoor and outdoor units and install positively so that
the units will not topple or fall.
CAUTION
(1) Do not install where there is the danger of com-
bustible gas leakage.
(2) Do not install near heat sources.
(3) If children under 10 years old may approach the
unit, take preventive measures so that they can-
not reach the unit.
Q'ty
1
1
[Indoor unit piping direction]
1
The piping can be connected in the 6 directions indicated in (Fig. 6). When
the piping is connected in direction 2, 3, 4 or 5, cut along the piping
1
groove in the side of the front cover with a hacksaw.
1
1
1 set
Fig. 6
1
1 set
1
2 Right outlet
1 Rear outlet
3 Bottom outlet
15 A
20 A
INSTALLATION DIAGRAM OF
INDOOR AND OUTDOOR UNITS
Fig. 7
[INDOOR UNIT]
2-2/5"(6 cm) or over
60"(150 cm) or over
95" (240 cm)
or over
Remote
control unit
Connection Cord
14AWG
[OUTDOOR UNIT]
24"(60 cm)
or over
4"(10 cm)
or over
24"(60 cm)
or over
2"(5 cm)
Mounting Support
or over
(Prepared On-site)
[Reverse cycle only]
5 Left
outlet
6 Left rear
Drain hose
outlet
4 Left bottom
Fig. 8
21-1/4" (54 cm)
outlet
Wall hook bracket
2"(5 cm)
or over
3- 3/5"(9 cm)
or over
(Wall cap)
Remote
control
unit holder
Tapping screw
(small)
2"(5 cm)
or over
10"(25 cm)
or over
Outdoor unit bottom