Unit installation

6.1.2 Additional installation site requirements of the outdoor unit in cold climates

6.1.3 Installation site requirements of the indoor unit

Installer reference guide
58
Protect the outdoor unit against direct snowfall and take care that the outdoor unit
is NEVER snowed up.
c
a
Snow cover or shed
b
Pedestal
c
Prevailing wind direction
d
Air outlet
In any case, provide at least 150  mm of free space below the unit. Additionally,
make sure the unit is positioned at least 100  mm above the maximum expected
level of snow. See
"6.3 Mounting the outdoor
In heavy snowfall areas it is very important to select an installation site where the
snow will NOT affect the unit. If lateral snowfall is possible, make sure that the heat
exchanger coil is NOT affected by the snow. If necessary, install a snow cover or
shed and a pedestal.
INFORMATION
Also read the precautions and requirements in the "General safety precautions"
chapter.
The indoor unit is designed for indoor installation only and for the following
ambient temperatures:
-
Space heating operation: 5~30°C
-
Space cooling operation: 5~35°C
-
Domestic hot water production: 5~35°C
INFORMATION
Cooling is only applicable in case of:
Reversible models
Heating only models + conversion kit (EKHVCONV2)
Mind the measurement guidelines:
Maximum height difference between indoor unit and outdoor
unit
Maximum total water piping length
a
c
b
4
unit" [
 64] for more details.
EPRA14~18DAV3+W1 + ETVH/X16S18+23DA6V+9W(G)
10 m
(a)
50 m
Daikin Altherma 3 H HT F
4P587502-1 – 2019.07