York YCAS Series Installation Operation & Maintenance page 57

Air-cooled screw liquid chillers
Hide thumbs Also See for YCAS Series:
Table of Contents

Advertisement

FIG. 18 – CONT'D
YORK INTERNATIONAL
ELEMENTARY DIAGRAM
VOLTAGE
ALL MODELS
W/O TRANS.
MODELS
WITH
TRANS.
*
* All primary and secondary wiring between transformer and control panel included.
CAUTION:
No Controls (relays, etc.)
should be mounted in the
Smart Panel enclosure or con-
nected to power supplies in the
control panel. Additionally,
control wiring not connected
to the Smart Panel should not
be run through the cabinet.
This could result in nuisance
faults.
CAUTION:
Any inductive devices (relays)
wired in series with the flow
switch for start/stop, into the
Alarm circuitry, or pilot relays
for pump starters wired
through motor contactor aux-
iliary contacts must be sup-
pressed with YORK P/N 031-
00808-000 suppressor across
the relay/contactor coil.
Any contacts connected to
flow switch inputs or BAS in-
puts on terminals 13 - 19 or
TB3, or any other terminals,
must be suppressed with a
YORK P/N 031-00808-000 sup-
pressor across the relay/con-
tactor coil.
CAUTION:
Control wiring connected to
the control panel should never
be run in the same conduit with
power wiring.
CONTROL POWER SUPPLY
CONTROL
MIN
UNIT
POWER
CIRCUIT
SUPPLY
AMP.
115-1-50/60
20A
-17
200-1-60
15A
-28
230-1-60
15A
-46
400-1-60
8A
-58
575-1-60
8A
FORM 201.18-NM1 (102)
7
MAX DUAL
NON-FUSED
ELEMENT
DISC.
FUSE SIZE
SWITCH SIZE
20A 250V
30A 240V
15A 250V
30A 240V
15A 250V
30A 240V
8A 600V
30A 480V
8A 600V
30A 600V
57