Configure Sensors - Bard MULTI-TEC W18AAPA Service Instructions Manual

Wall-mount air conditioner part of the bard free cooling system
Table of Contents

Advertisement

3) Press the UP or DOWN keys to scroll to the
Settings menu; press ENTER key.
4) Press UP or DOWN keys to scroll to Date/Time
menu; press ENTER key.
5) Press UP or DOWN keys to scroll to Date/Time
change.
6) Press ENTER key to scroll to the desired value
to be changed (see Figure 32).
7) Press UP or DOWN keys to change the value.
8) Press ENTER key to save and to scroll to top of
screen.
9) Press UP or DOWN keys to scroll to Timezone
(if applicable). Follow steps 6-8 to change
timezone.
10) Press ESCAPE key several times to return to
Main Menu screen.
NOTE: The LC6000 will sync the time and date
configured to each of the wall-mount units once
communication is established.
FIGURE 32
Setting Controller Date and Time

5. Configure Sensors

The system will need to be configured for the
number of temperature and humidity sensors
installed. The system is shipped with one
combination temperature and humidity sensor.
LC6000 Controller Display and Interface (Status Screen Shown)
ALARM KEY
MENU KEY
ESCAPE KEY
LC6000 interface key functions are the same as those shown for the TEC-EYE in Figure 28 on page 36.
Additional combination sensors may be purchased
or alternatively, temperature-only sensors may be
purchased instead. The LC is capable of utilizing
five temperature sensors and four humidity sensors.
The system will need to be configured for the
various configurations.
If necessary, the sensors could be calibrated at this
time too. For information on calibrating the sensors
(adjusting the offset), see page 44.
To enable/disable Zone 1 Indoor Humidity:
1) Press MENU key to go to the Main Menu
screen.
2) Press UP or DOWN keys and ENTER key to
enter USER password 2000.
3) Press UP or DOWN keys to scroll to IO Config;
press ENTER key.
4) Press UP or DOWN keys to scroll to Z1 Indoor
Hum C4.
5) Press ENTER key to scroll to Enable (see
Figure 33).
6) Press UP or DOWN key to change value to ON
to enable sensor (or change value to OFF to
disable sensor).
Enable/Disable Zone 1 Indoor Humidity Sensor
FIGURE 34
FIGURE 33
UP KEY
ENTER KEY
DOWN KEY
Manual 2100-676D
Page
39 of 45

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Multi-tec w24aapaMulti-tec w24aapbMulti-tec w24aapcMulti-tec w30aapaMulti-tec w30aapbMulti-tec w30aapc ... Show all

Table of Contents