MAP 5000
Warning!
When installing the power supply, ensure that the ground wire from the AC terminal block is
!
connected to the ground connection point as shown in , page 22.
The ground wire from the AC terminal block to the power supply does not provide an earth
ground for the enclosure. It only provides an earth ground for the power supply.
Warning!
Electricity
!
Once the terminal block connected to the AC terminal block has been put into the power
supply, do not remove it anymore. Never remove the terminal block connected to the AC
terminal block from the power supply during operation.
Installing the thermistor cable
The thermistor cable is used to adjust the battery charge voltage to compensate for the air
temperature around the batteries.
1.
2.
Notice!
In case more than one enclosure is used, mount the thermistor cable in the enclosure in
which the power supply is placed.
Mounting the thermistor
See also
2.6

Installing the TAE box

4
Bosch Security Systems B.V.
Plug the thermistor cable into the power supply to the terminal marked
Mount the thermistor on the inside rear of the enclosure right on the top of the two
batteries.
Technical Specifications, page 68
If the TAE Box is not mounted on the wall behind the enclosure, mount the TAE Box to
the enclosure back wall either horizontally or vertically as desired.