Daikin VRV III-S RXYMQ6PV4A Service Manual page 34

For high outdoor temperature use, r-410a
Table of Contents

Advertisement

SiME34-608
Ceiling Mounted Duct Type
Model
1 Cooling Capacity (19.5°CWB)
2 Cooling Capacity (19.0°CWB)
3 Heating Capacity
Casing
Dimensions: (H×W×D)
Rows×Stages×Fin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output × Number
of Units
Fan
Air Flow Rate (H/L)
External Static
Pressure 50 / 60Hz
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Gas Pipes
Piping
Connections
Drain Pipe
Machine Weight (Mass)
7 Sound Level (H/L) (220V)
Safety Devices
Refrigerant Control
Connectable outdoor unit
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m, level difference;
4 External static pressure is changeable to change over the connectors inside electrical box, this pressure
5 Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its
6 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
7 Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center. These
Specifications
FXMQ100MAVE
RT
kcal/h
Btu/h
kW
kW
RT
kcal/h
Btu/h
kW
Galvanized Steel Plate
mm
390×1,110×690
mm
2D11/2D3AG1VE
Sirocco Fan
W
m³/min
cfm
Pa
157/172-98/98
Direct Drive
Microprocessor Thermostat for Cooling and Heating
Glass Fiber
φ
mm
9.5 (Flare Connection)
φ
mm
15.9 (Flare Connection)
mm
External Dia. 32
(
Internal Dia. 25
kg
dBA
Thermal Fuse for Fan Motor
Electronic Expansion Valve
R-410A P Series
Operation Manual, Installation Manual, Drain Hose, Clamp
Metal, Insulation for Fitting, Sealing Pads, Clamps, Screws.
difference: 0m.
difference: 0m.
0m. (Heat pump only)
means
"High static pressure-Standard".
colorimetric method (gravity method) 50% or more.
values are normally somewhat higher during actual operation as a result of ambient conditions.
3.3
10,000
39,600
11.6
11.2
3.6
10,800
42,700
12.5
3×16×2.0
0.319
270×1
29/23
1,024/812
4
5
VP25
)
63
43/39
Fuse,
Operation Manual, Installation Manual, Drain Hose, Clamp
Metal, Insulation for Fitting, Sealing Pads, Clamps, Screws.
C: 3D038814A
Specifications
FXMQ125MAVE
4.1
12,500
49,500
14.5
14.0
4.5
13,800
54,600
16.0
Galvanized Steel Plate
390×1,110×690
3×16×2.0
0.319
2D11/2D3AF1VE
Sirocco Fan
430×1
36/29
1,271/1,024
191/245-152/172
4
Direct Drive
Microprocessor Thermostat for Cooling and Heating
Glass Fiber
5
φ
9.5 (Flare Connection)
φ
15.9 (Flare Connection)
VP25
External Dia. 32
(
)
Internal Dia. 25
65
45/42
Fuse,
Thermal Fuse for Fan Motor
Electronic Expansion Valve
R-410A P Series
Conversion Formulae
RT=kW×0.284
kcal/h=kW×860
Btu/h=kW×3412
cfm=m³/min×35.3
23