Daikin VRV III-S RXYMQ6PV4A Service Manual page 213

For high outdoor temperature use, r-410a
Table of Contents

Advertisement

Troubleshooting by Indication on the Unified ON/OFF Controller
[CHECK 3]
Check for Fan Motor Connector
(1) Turn the power supply off.
(2) With the fan motor connector disconnected, measure the resistance between each pin, then
202
make sure that the resistance is more than the value mentioned in the following table.
1 White
2 Orange
3 Brown
GND
4 Blue
5
6
7 Red
Measurement point
Judgment
1 - 4
1MΩ or more
2 - 4
100kΩ or more
3 - 4
100Ω or more
4 - 7
100kΩ or more
SiME34-608