Troubleshooting By Indication On The Centralized Remote Controller; Ue" Malfunction Of Transmission Between Centralized; Remote Controller And Indoor Unit - Daikin VRV III-S RXYMQ6PV4A Service Manual

For high outdoor temperature use, r-410a
Table of Contents

Advertisement

Troubleshooting by Indication on the Centralized Remote Controller

4.
Troubleshooting by Indication on the Centralized
Remote Controller
"UE "
4.1
Malfunction of Transmission between Centralized

Remote Controller and Indoor Unit

UE
Remote Controller
Display
Applicable
AII indoor unit models
Centralized Remote Controller
Models
Method of
Microcomputer checks if transmission between indoor unit and central remote controller is
Malfunction
normal.
Detection
Malfunction
When transmission is not carried out normally for a certain amount of time
Decision
Conditions
Supposed
Causes
Troubleshooting
188
Malfunction of transmission between optional controllers for centralized control and indoor unit
Connector for setting master controller is disconnected.
Failure of PC board for central remote controller
Defect of indoor unit PC board
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Has
an indoor unit once
connected been remove
or its address
changed?
NO
Is the
power supply turned
on for indoor units displaying
malfunction?
YES
Is
transmission wiring
disconnected or wired
incorrectly?
YES
Is transmission
with all indoor units
malfunctioning?
YES
Is the
transmission wiring
with the master controller
disconnected or wired
incorrectly?
YES
Is the
master controller's
connector for setting
master controller
disconnected?
YES
YES
NO
NO
Is the group
NO
No. of malfunctioning
indoor units set?
YES
NO
NO
SiME34-608
Reset power supply
simultaneously for all optional
controllers for centralized
control.
Turn indoor unit's power
supply.
Fix the wiring correctly.
NO
Set the group No. correctly.
Replace indoor unit PC
board.
Fix the wiring correctly.
Connect the connector
correctly.
Replace the central PC board.