Daikin VRV III-S RXYMQ6PV4A Service Manual page 133

For high outdoor temperature use, r-410a
Table of Contents

Advertisement

Troubleshooting by Remote Controller
Malfunction
code
Indoor Unit
A0
A1
A3
A6
A7
A9
AF
AJ
C4
C5
C9
CA
CJ
Outdoor Unit
E1
E3
E4
E5
E6
E7
E9
F3
F6
H3
H4
H7
H9
J2
J3
J5
J6
J7
J9
JA
JC
L0
L1
L4
L5
L8
L9
122
Operation
Inspection
Unit No.
lamp
display
9
9
9
9
9
9
9
9
8
9
9
9
8
7
9
9
9
9
9
9
9
9
9
9
8
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
8
7
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
Malfunction contents
Error of external protection device
9
PC board defect, E
9
Malfunction of drain level control system (S1L)
9
Fan motor (M1F) lock, overload
9
Malfunction of swing flap motor (M1S)
9
Malfunction of moving part of electronic expansion
9
valve (Y1E)
Drain level above limit
9
Malfunction of capacity setting
9
Malfunction of thermistor (R2T) for heat exchange
9
(loose connection, disconnection, short circuit, failure)
Malfunction of thermistor (R3T) for gas pipes (loose
9
connection, disconnection, short circuit, failure)
Malfunction of thermistor (R1T) for air inlet (loose
9
connection, disconnection, short circuit, failure)
Malfunction of thermistor for air outlet (loose
9
connection, disconnection, short circuit, failure)
Malfunction of thermostat sensor in remote controller
8
PC board defect
9
Actuation of high pressure switch
9
Actuation of low pressure sensor
9
Compressor motor lock
9
Standard compressor lock or over current
9
Malfunction of outdoor unit fan motor
9
Malfunction of moving part of electronic expansion
9
valve (Y1E, Y2E)
Abnormal discharge pipe temperature
9
Refrigerant overcharged
9
Failure of high pressure switch
9
Actuation of low pressure switch
9
Abnormal outdoor fan motor signal
9
Malfunction of thermistor (R1T) for outdoor air (loose
9
connection, disconnection, short circuit, failure)
Current sensor malfunction
9
Malfunction of discharge pipe thermistor (R2T) (loose
9
connection, disconnection, short circuit, failure)
Malfunction of thermistor (R3T, R5T) for suction pipe
9
(loose connection, disconnection, short circuit,
failure)
Malfunction of thermistor (R4T) for heat exchanger
9
(loose connection, disconnection, short circuit,
failure)
Malfunction of receiver outlet liquid pipe thermistor (R7T)
9
Malfunction of subcooling heat exchanger gas pipe
9
thermistor (R5T)
Malfunction of discharge pipe pressure sensor
9
Malfunction of suction pipe pressure sensor
9
Inverter system error
9
Malfunction of PC board
9
Malfunction of inverter radiating fin temperature rise
9
DC output overcurrent of inverter compressor
9
Inverter current abnormal
9
Inverter start up error
9
8: ON
7: OFF
2
PROM defect
Troubleshooting
SiME34-608
9: Blink
Page
Referred
128
129
130
132
133
135
137
138
139
140
141
142
143
144
145
147
149
150
151
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents