Table 1. Masonry Vitreous Tile-Lined Chimney (not metal lined)
Chimneys not exposed to the outdoors below the roof line. (5" dia. vent adapter must be used)
Additional
Boiler
Gas Appliance
Model(s) †
in Venting System
VH-90
No
VH-120
VH-150
VH-180
VH-180
No
VH-90
Yes
VH-120
VH-150
VH-180
VH-150
Yes
VH-180
Table 2. Type "B" Venting and Metal-Lined Masonry Chimney
UL LISTED MATERIALS ONLY. (5" dia. vent adapter must be used)
Additional
Boiler
Gas Appliance
Model(s) †
in Venting System
VH-90
No
VH-120
VH-150
VH-180
VH-90
No
VH-120
VH-150
VH-180
VH-90
Yes
VH-120
VH-150
VH-180
VH-120
Yes
VH-150
VH-180
* Also see Z223.1 Part 7 and Part 11 for use of mentioned tables.
† Only Victory II boiler models shown for each application permitted to be installed in that manner specified.
Connector
Type "B"
1. Connector diameter must be upsized to 7".
2. Chimney height limits: Min. 15 ft., Max. 30 ft.
3. Lateral length restriction applies (see Table 11-3)
4. Internal area of chimney: Min. 50 sq. in.,
Max. 269 sq. in.
Single-wall
1. Connector diameter must be upsized to 7".
2. Chimney height limits: Min. 15 ft., Max. 30 ft.
3. Max. lateral length may not exceed 2 ft.
4. Internal area of chimney: Min. 50 sq. in.,
Max. 269 sq. in.
Type "B"
1. See Table 11-8 for chimney height and connector
length restrictions.
2. Connector may have to be upsized to 6" diameter
to meet requirement of 11-8.
Single-wall
1. See Table 11-9 for chimney height and connector
length restrictions.
2. Connector may have to be upsized to 6" diameter
to meet requirement of 11-9.
Connector
Type "B"
See Table 11-1 for minimum and maximum of vent
height and lateral length restriction.
Single-wall
See Table 11-2 for minimum and maximum of vent
height and lateral length restriction.
Type "B"
1. See Table 11-6 for vent height and connector
length restrictions.
2. Connector and vent diameter may have to be
increased to 6" or 7" to meet requirement of
Table 11-6.
Single-wall
1. See Table 11-7 for vent height and connector
length restrictions.
2. Connector and vent diameter may have to be
increased to 6" to meet requirement of Table 11-7.
Requirements*
Requirements*
National Fuel Gas Code
Reference Table No.*
(ANSI Z223.1)
11-3
11-4
11-8
11-9
National Fuel Gas Code
Reference Table No.*
(ANSI Z223.1)
11-1
11-2
11-6
11-7