15.1.4
Compressor Overheating Prevention Control
Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The changes of
frequency are as below.
If compressor discharge temperature exceeds 103
will be blinking. ("F97" is indicated.)
15.1.5
Low Pressure Prevention Control (Gas Leakage Detection)
a. Control start conditions
For 5 minutes, the compressor continuously operates and outdoor total current is between 0.75A and 0.95A.
During Cooling and Soft Dry operations:
Indoor suction temperature - indoor piping temperature is below 4°C.
During Heating operations :
Indoor piping temperature - indoor suction is under 5°C.
b. Control contents
Compressor stops (and restart after 3 minutes).
If the conditions above happen 2 times within 20 minutes, the unit will:
Stop operation
o
Timer LED blinks and "F91" indicated.
o
15.1.6
Low Frequency Protection Control 1
When the compressor operate at frequency lower than 24 Hz continued for 240 minutes, the operation frequency
will be changed to 23 Hz for 2 minutes.
15.1.7
Low Frequency Protection Control 2
When all the below conditions comply, the compressor frequency will change to lower frequency.
Indoor heat exchanger (°C)
103°C
99°C
96°C
Comp. Discharge temperature
Temperature, T, for:
Indoor intake air (°C)
Outdoor air (°C)
°
C, compressor will be stopped, occurs 4 times per 20 minutes, timer LED
Compressor = OFF
Compressor Frequency
Reduce
Compressor Frequency
Maintain
Free
Cooling / Soft Dry
T < 14 or T ≥ 30
T < 13 or T ≥ 38
T < 30
74
88°C
87°C
86°C
Heating
T < 14 or T ≥ 28
T < 4 or T ≥ 24
T < 0