Download Print this page

Honeywell GENT S4 Data And Installation page 2

Mains powered interface
Hide thumbs Also See for GENT S4:

Advertisement

Data and Installation
EN54-17 : 2005
V
max
(section 4.8)
V
nom
data:
V
min
V
SO max
V
SO min
Emission
BS EN61000-6-3: 2007 EMC for
residential, commercial & light
Industry.
Immunity
BS EN50130-4: 1996 +
A1:1998 +A2 2003
for alarm systems
Maximum number
8 (with fully sectored outputs)
per loop
Load factor
1
(1000 maximum)
Terminals
3-way device (terminals
provided for spur or sub-loop)
&
Repetitive switching of capacitive loads
greater than 1500uF is not possible and will result
in the thermal protection circuit automatically
reducing the output voltage.
Terminals for Auxiliary output
and Zone/Sector circuits
Quick reference label
Door lock
Backbox to door earth lead
2
www.acornfiresecurity.com
42V
I
0.4A
C max
40V
I
1A
S max
24V
20mA
I
L max
16V
Z
0.1W
C max
8V
Top and rear
cable entry points
Metal
screen
AUX O/P
SECTOR / ZONE1
SECTOR / ZONE2
SECTOR / ZONE3
SECTOR / ZONE4
LOOP
0C LC 01 L1 02 L2
+
-
+
-
S+
S-
Z+ Z-
S+
S-
Z+ Z-
S+
S-
Z+ Z-
S+
S-
Z+ Z-
FS6
PB6
PB2
PB3
PB4
PB5
PB1
T3.16A
CERAMIC
ANTI-SURGE
P1
Mains Powered
Interface Unit Mk 3
Batteries are fitted here
during commissioning
www.acornfiresecurity.com
S4 Mains powered interface unit
Features
¨
Fail-safe operation
A fail-safe operation is available on all sectored
outputs, if loop communications are lost for a defined
duration then the sector outputs will be turned ON.
Sector outputs will turn OFF immediately when
communication is restored.
¨
Synchronisation
Adjustable synchronisation pulses can be selected
for all sector outputs to synchronise the operation of
devices such as xenon strobes or speech sounders.
¨
Auxiliary Output
The Auxiliary output can be programmed to
automatically turn OFF when a mains failure occurs
to preserve battery capacity. The output can also be
programmed to provide a reset pulse when a fire
reset occurs.
Earth points for DIN rail modules
4 Backbox mounting points
DIN rail for optional modules
Earth points for wiring
Terminals for mains cable
+ mains fuse
L
N
P3
Mains interface PCB
(Not all components shown)
Loop terminals
DANGER
DO NOT
REMOVE
Battery connector
P7
Battery fuse
FS8 F3.16A
QUICK
BLOW
SW1 - POWER UP
Battery 'Power up'
push button
IS Galvanic
Isolator
Relay
4188-968 issue 2_Part 1_09-10_S4 mains interface
Surge
Protection

Advertisement

loading

This manual is also suitable for:

S4-34440-02S4-34440-12