Honeywell GENT S4 Data And Installation page 10

Mains powered interface
Hide thumbs Also See for GENT S4:

Advertisement

Commissioning information
Supervisory Input mode
This example sets the respective channel as a Supervisory input.
Mode
settings
Supervisory input
Input delay
Input normally
Fault Input mode
This example shows how to set a channel as a Fault input.
Mode
settings
Fault input
Input delay
Input normally
Fire Input mode
This example shows how to set a channel as a Fire input.
Mode
settings
Fire Input
Input delay
Input normally
6
www.acornfiresecurity.com
notes
The Input Delay is the time before the input is
accepted by the interface, this will filter any noise or
spurious signals, commonly know as "bounce". This
time is the debounce period. The input delay timeout
can be any value in the range 0 to 36 seconds.
The input channel can be configured to operate with
normally open or normally closed contacts.
Note normally closed operation should be selected if
fail safe contact monitoring is required.
notes
As described for Supervisory input.
As described for Supervisory input.
notes
As described for Supervisory input.
As described for Supervisory input .
www.acornfiresecurity.com
S4 Mains powered interface unit
4188-968 issue 2_Part 2_09-10_S4 mains interface