Toshiba RAV-SP1104AT8-E1 Service Manual page 89

Table of Contents

Advertisement

CAUTION
1.
Do not put the crescent wrench on the cap or cover.
The valve may break.
2.
If applying excessive torque, the nut may break
according to some installation conditions.
NO GOOD
Cover
Cap
• After the installation work, be sure to check for gas
leaks of the pipe connections with nitrogen.
• Pressure of R410A is higher than that of R22 (Approx.
1.6 times).
Therefore, using a torque wrench, tighten the flare
pipe connecting sections that connect the indoor/
outdoor units at the specified tightening torque.
Incomplete connections may cause not only a gas
leak, but also trouble with the refrigeration cycle.
Do not apply refrigerating machine oil to the flared
surface.
EN-129
- 65 -
Refrigerant Pipe Length
Single
Allowable pipe length (m)
Total length L
75
Pipe diameter (mm)
Gas side
Ø15.9
Simultaneous twin, triple
Allowable pipe length (m)
Total length
1 +
2
System
Model
1 +
3
1 +
4
Maximum
SP110
50
TWIN
SP140,
50
SP160
TRIPLE
SP160 only
50
System
Model
Gas side
SP110
Ø15.9
TWIN
SP140,
Ø15.9
SP160
TRIPLE
SP160 only
Ø15.9
Figure of Single
Figure of Simultaneous twin
Indoor Unit
Outdoor Unit
Outdoor Unit
Height difference (Indoor-outdoor H) (m)
Indoor unit: Upper
Outdoor unit: Lower
30
Number of bent portions
Liquid side
Ø9.5
Height difference (m)
Distributed
Distributed
Indoor-outdoor H
pipes
pipes
2
3 –
2
Indoor unit:
Outdoor
3
4 –
2
Upper
unit: Upper
4
4 –
3
Maximum
Maximum
15
10
30
15
10
30
15
10
30
Pipe diameter (mm)
Main pipe
Branching pipe
Liquid side
Gas side
Liquid side
Ø9.5
Ø12.7
Ø6.4
Ø9.5
Ø15.9
Ø9.5
Ø9.5
Ø12.7
Ø6.4
Figure of Simultaneous triple
Indoor Unit
Indoor Unit
Indoor Unit
Indoor Unit
Distributor
Outdoor Unit
2
2
3
1
30
10 or less
Indoor-
indoor (Δh)
30
0.5
30
0.5
30
0.5
Number of
bent portions
10 or less
10 or less
10 or less
Indoor Unit
4
3
Distributor
1
EN-130