Toshiba RAV-SP1104AT8-E1 Service Manual page 43

Table of Contents

Advertisement

Lamp indication
Operation Timer
Ready
Alternate flash
Operation Timer
Ready
Alternate flash
Operation Timer
Ready
Simultaneous flash
Operation Timer
Ready
Simultaneous flash
Operation Timer
Ready
Flash
Operation Timer
Ready
Simultaneous flash
Operation Timer
Ready
Simultaneous flash
∗1: These are representative examples and the check code differs according to the outdoor unit to be combined.
Check code
F01
Heat exchanger sensor (TCJ) error
F02
Heat exchanger sensor (TC) error
P10
Heat exchanger sensor (TA) error
F04
Discharge temp. sensor (TD) error
F06
Temp. sensor (TE) error
F07
Temp. sensor (TL) error
F08
Temp. sensor (TO) error
F12
Temp. sensor (TS) error
F13
Temp. sensor (TH) error
F15
Temp. Sensor miswiring (TE, TS)
F29
Indoor EEPROM error
F31
Outdoor EEPROM error
H01
Compressor break down
H02
Compressor lock
H03
Current detection circuit error
H04
Case thermostat worked.
PS pressure sensor error,
H06
low pressure protective operation
L03
Duplicated header indoor units
There is indoor unit of group connection
L07
in individual indoor unit.
L08
Unsetting of group address
Missed setting
L09
(Unset indoor capacity)
L10
Unset model type (Service board)
L20
Duplicated indoor central addresses
L29
Outdoor unit and other error
L30
Outside interlock error
L31
Negative phase error
Cause of trouble occurrence
Outdoor compressor system error
} Power supply, outdoor P.C. board error
} Compressor overheat, outdoor wiring error
– 43 –
Indoor unit sensor error
Sensor error of outdoor unit
Outdoor unit
low pressure system error
→ AUTO address
* If group construction and
address are not normal
power supply turned on,
automatically goes to
address setup mode.
∗1
∗1