Appendix
Code
Parameter
F.71
Fault: Flow sensor
F.72
Fault: Flow/return sensor
F.73
Fault: Water press. sensor
F.74
Fault: Water press. sensor
F.75
Fault: Pump/ water shortage
F.77
Fault: Flue non-ret. valve/condens. pump
F.78
Interrupt.: DHW outlet sensor on ext. contr.
F.80
Fault: actoSTOR inlet sensor
F.81
Fault: cylinder charging pump
F.82
Fault: Ext. current anode
F.83
Fault: NTC temp. gradient
F.84
Fault: NTC temp. diff. implausible
F.85
Fault: NTCs fitted incorrectly
F.90
Fault: Communication
F.94
Fault: Vortex and differential pressure
LED
actoSTOR electronics status
actoSTOR
module
Commu-
Communication fault
nication
fault
42
Possible causes
Flow temperature sensor signalling constant value:
–
Flow temperature sensor incorrectly positioned at flow pipe
–
Flow temperature sensor defective
Flow/return NTC temperature difference too great → flow and/or return
temperature sensor defective
Interruption/short circuit of water pressure sensor, interruption/short
circuit to GND in supply line to water pressure sensor or water pressure
sensor defective
The line to the water pressure sensor has a short circuit to 5 V/24 V or
internal fault in the water pressure sensor
Water pressure sensor and/or pump defective, air in the heating installa-
tion, insufficient water in the product; connect external expansion vessel
to the return
No response from flue non-return flap or condensate pump defective
UK link box is connected but the domestic hot water NTC is not bridged
Only in conjunction with F.91
NTC defective, NTC cable defective, defective plug connection on NTC,
defective plug connection on the actoSTOR electronics
Sensor plug has short to earth to the housing, short circuit in cable har-
ness, sensor defective
Only in conjunction with F.91
Cylinder is not fully charged after specified time.
–
Check cylinder charging sensor and cylinder sensor
–
Air in the actoSTOR pump
–
Inspect cable harness for pump
–
Check the impeller sensor and/or limiter in the product
–
Prioritising diverter valve defective
–
Secondary heat exchanger blocked
–
Pump defective
External current anode not connected:
–
X43 edge connector with bridge missing from the PCB
External current anode connected:
–
Power supply to the external current anode was interrupted
–
Cable between PCB and external current anode defective
–
External current anode defective
When the burner starts, the temperature change registered at the flow
and/or return temperature sensor is non-existent or too small.
–
Insufficient water in product
–
Flow or return temperature sensor not in correct position at pipe
Flow and return temperature sensors returning implausible values.
–
Flow and return temperature sensors have been inverted
–
Flow and return temperature sensors have not been correctly in-
stalled
The flow and/or return temperature sensors have been installed on the
same pipe/incorrect pipe
Check the cable harness from the product to the actoSTOR module
(PEBus).
If the product is to be operated without an actoSTOR module, set
D.092 = 0.
Check: Pump (function), cable harness, plug, sensors.
LED on: Communication OK
LED flashing: Communication not OK
LED off: No power supply
Communication fault between display and PCB in the electronics box
Installation and maintenance instructions ecoTEC exclusive 0020189875_01