Setup; Indication Of The Switching Status; Function Table - Siemens SITRANS L Series Operating Instructions Manual

Capacitance transmitters
Hide thumbs Also See for SITRANS L Series:
Table of Contents

Advertisement

Setup

6.1

Indication of the switching status

The switching status of the electronics can be checked via the 360° status indication
(LEDs) integrated in the upper part of the housing.
The colours of the 360° status indication have the following meaning: (Default
setting)
6.2

Function table

The following table provides an overview of the switching conditions depending on
the set mode and the level (factory setting).
Coverage
Covered
Uncovered
SITRANS LCS050
Operating Instructions, 02/2021,
A5E50859888
Green lights up - power supply connected, transmitter output high-impedance
Green flashing - Maintenance required
Yellow lights up - power supply connected, transmitter output low impedance
Red lights - shortcircuit or overload in the load circuit (transmitter output high-
impedance)
Red flashing - Error at transmitter or electronics (transmitter output high
impedance) or device is in simulation
Switching status
Output 1
open
closed
a
Switching status
Output 2
closed
open
b
c
Control lamp
Green
Yellow
6
17

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitrans lcs050

Table of Contents