Draining The Boiler On The Heating Water Side - Viessmann Vitodens 222-F Installation Instructions For Contractors

Gas condensing storage combi boiler natural gas and lpg version
Table of Contents

Advertisement

Troubleshooting
Maintenance
(cont.)

Draining the boiler on the heating water side

!
Please note
Risk of scalding.
Residual water will escape when the boiler or
one of the following components is fitted or
removed:
Water-filled pipework
Circulation pumps
Plate heat exchanger
Components fitted in the heating water or
DHW circuit
Water ingress can result in damage to other
components.
Protect the following components against
ingress of water:
Control unit (in particular in the service posi-
tion)
Electrical components
Plug-in connections
Cables and leads
Only drain the boiler or heating system when the
boiler water or cylinder temperature has drop-
ped below 40 °C.
A
Fig. 43
1. Close the shut-off valves on the heating water side.
2. Route hose at drain valve
tainer or drain outlet.
68
into a suitable con-
A
3. Open drain valve
and drain the boiler as much
A
as required.