Gas Connection - Viessmann Vitodens 222-F Installation Instructions For Contractors

Gas condensing storage combi boiler natural gas and lpg version
Table of Contents

Advertisement

Installing the boiler
Flue gas connection
Do not carry out commissioning until the following
conditions are met:
Free passage through the flue gas pipes.
Flue system with positive pressure is gas-tight.
Apertures for ensuring sufficient combustion air sup-
ply are open and cannot be closed off.
Applicable regulations on installing and commission-
ing flue systems have been followed.

Gas connection

A
Fig. 8
1. Seal gas shut-off valve
Information on operation with LPG
Install an external safety solenoid valve if the boiler
is installed below ground level.
2. Carry out a tightness test.
Note
Only use suitable and approved leak detection
agents (EN 14291) and devices for the tightness
test. Leak detection agents with unsuitable constit-
uents (e.g. nitrides, sulphides) can cause material
damage.
Remove leak detection agent residues after test-
ing.
!
Please note
Excessive test pressure will damage the
boiler and the gas train.
Max. test pressure 150 mbar (15 kPa). If a
higher pressure is required for tightness
tests, disconnect the boiler and the gas train
from the main supply pipe (undo the fitting).
14
(cont.)
A
to the gas connection.
A
Danger
Leaking or blocked flue systems or an insuffi-
cient supply of combustion air cause life threat-
ening poisoning due to carbon monoxide in the
flue gas.
Ensure the flue system functions correctly. Aper-
tures for combustion air supply must not be able
to be closed off.
A
3. Purge the gas line.

Advertisement

Table of Contents
loading

This manual is also suitable for:

B2sb

Table of Contents